7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another (L, N)
● Connect the output terminals, signaling contact, I
Test (C)
● Connect the output terminals, signaling contact and current monitoring terminal with one
another and measure with respect to PE
Table 7- 1
Test voltage for 6EP7133-6AB00-0BN0 and 6EP7133-6AE00-0BN0
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
36
Test voltage diagram
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
2200 V DC
1 s
1500 V AC
1 s
2200 V DC
1 s
1500 V AC
and PE with one another
Monitor
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 V DC
700 V DC
1500 V AC
500 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
Manual, 03.2018, A5E43207434