Engineering and remote access
7.6 Cyclic and acyclic data
Index 6: Device information (reading)
Data
MLFB/Order number
Product state
Fill byte(s)
SW version
Serial number
Index 7: Hardware settings (reading)
Data
Utarget1 potentiometer [10mV]
Ilimit1 potentiometer [10mA]
Output Enable1 manual button (0/255)
Fill byte(s)
Utarget2 potentiometer [10mV]
Ilimit2 potentiometer [10mA]
Output Enable2 manual button (0/255)
Fill byte(s)
Utarget3 potentiometer [10mV]
192
Description
Article No./Order number
Product release
-
Software version
Serial number
Description
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Actual DIP switch state for output 1:
0 = Manually shut down
255 = Manually switched on
-
Manually set setpoint of the output voltage at out-
put 2: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Manually set threshold of the output current at
output 2. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Actual DIP switch state for output 2:
0 = Manually shut down
255 = Manually switched on
-
Manually set setpoint of the output voltage at out-
put 3: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Data type
VisibleString(20)
Unsigned8
Unsigned8
Unsigned32
VisibleString(16)
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned16