Siemens PSU8600 Manual page 173

Sitop power supply
Hide thumbs Also See for PSU8600:
Table of Contents

Advertisement

Output data SITOP PSU8600
Slot
Subslot Data
0
2
Device Reset_In
Device Ithreshold
[1 %]
System overload alarm
threshold time [ms]
Main power outage
alarm threshold time
[ms]
Buffering disable
Data block active
0
3
Output Utarget
[10 mV]
Output Ilimit [10 mA]
Output Ithreshold
Channel1 Output Ena-
ble
Channel1 Reset_In
Data block active
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Description
Status of input "Reset_In": This
input resets all active faults and
reactivates all of the outputs that
are in the "Ready for restart" oper-
ating state.
Prewarning threshold total current
of the SITOP PSU8600.
Time delay before an alarm is
issued after a system overload was
detected.
Time delay before an alarm is
issued after failure of the power
supply voltage (power supply
changes into the "Buffer mode").
Buffer module was deactivated via
control command.
Indicator: Data block contains valid
data.
Currently set setpoint of the output
voltage.
Response threshold value of the
output current for the particular
output. When this is exceeded, the
output current is interpreted as
having an overload condition and is
shut down with a time delay - or
limited.
Prewarning threshold of the config-
ured response threshold for the
output current in %. An alarm is
initiated when the actual output
current exceeds this value. Opera-
tion is continued without any re-
strictions. Prewarning is
deactivated by entering "0 %".
Switches the output on or off. A
possible automatic shutdown due
to overload or power failure is not
taken into account.
Resets an overload shutdown for
this output
Indicator: Data block contains valid
data.
Engineering and remote access
7.6 Cyclic and acyclic data
Value range
Data size
0 = false, >0 = true
Unsigned8
(default setting: false)
0 - 100 %
Unsigned8
(default setting: 90 %)
0 - 60 000 ms
Unsigned16
(default setting:
5 000 ms)
0 - 1 000 ms
Unsigned16
(default setting: 0 ms)
0 = false, >0 = true
Unsigned8
(default setting: false)
0 = false, >0 = true
Unsigned8
(default setting: false)
4.0 V - 28.0 V
Unsigned16
(default setting:
24.0 V)
Output 5 A:
Unsigned16
0.0 A - 5.0 A
(default setting: 5.0 A)
Output 10 A:
0.0 A - 10 A
(default setting: 10 A)
0 - 100 %
Unsigned8
(default setting: 90 %)
0 = false, >0 = true
Unsigned8
(default setting: false)
0 = false, >0 = true
Unsigned8
(default setting: false)
0 = false, >0 = true
Unsigned8
(default setting: false)
173