Test Voltage - Siemens LOGO!Power Series Operating Instructions Manual

Table of Contents

Advertisement

Safety, approvals, EMC

7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Test (A)
● Connect the input terminals to one another
● Connect the output terminals to one another
Table 7- 1
Test voltage
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
42
Test voltage diagram
Test time
60 s
60 s
1 s
1 s
1 s
1 s
Prim ↔ sec (A)
4200 VDC
3000 VAC
2200 VDC
1500 VAC
2200 VDC
1500 VAC
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629