Operator control at the device
3.3 Overload shutdown and carrying out a reset
Remote reset via terminal RST
The reset can be alternatively carried out using a remote reset signal. The non-isolated 24 V
input (referred to terminal "0V" of the device) at terminal "RST" can be used. A reset is
carried out for an input level of > 15 V for at least 100 ms.
Procedure
Connect a voltage of > 15 V for at least 100 ms to terminal "RST".
The reset is carried out.
Note
If a switch-on delay of the output is defined (this function is only available when operated
together with a CNX8600 expansion module) when switching on, this is not taken into
account for a reset initiated using a remote reset signal.
Note
The rising edge of the reset signal is evaluated; this means for an additional reset signal, the
voltage level must first drop down to below 13 V.
60
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76