Technical data

9.2 Output data

Integrated input fuse
Protection in the line feeder cable
(IEC 898)
Can be expanded by a maximum of 2 buffer modules
1)
in conjunction with CNX8600 expansion module: Prioritized supply of the output when the power fails, can be selected
2)
using DIP switch.
Figure 9-1
9.2
Output data
Basic device
6EP3436-8SB00-2AY0
Output
Regulated, isolated DC voltage
Number of out-
1
1)
puts
Rated voltage
24 V
U
DC
out rated
Total tolerance,
3%
static ±
Static line regula-
0.2%
tion, approx.
Static load regu-
0.1 %
lation, approx.
Residual ripple in
100 mV
the load range
peak-peak, max.
286
Basic device
6EP3436-8SB00-2AY0
None
Required: 3-pole, coupled miniature
circuit breaker 6 - 16 A characteristic C
or circuit breaker 3RV2011-1DA10
(setting 3 A) or 3RV2711-1DD10
(UL489-listed, DIVQ)
Power failure buffering
Basic device
6EP3437-8SB00-2AY0
1
1)
24 V
3 %
0.2%
0.1 %
100 mV
Basic device
6EP3437-8SB00-2AY0
None
required: 3-pole, coupled miniature
circuit breaker 10 - 16 A characteris-
tic C or circuit breaker 3RV2011-1DA10
(setting 3 A) or 3RV2711-1DD10
(UL489-listed, DIVQ)
Expansion module
6EP4436-8XB00-0CY0
4
24 V
3%
0.2%
0.1 %
100 mV
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Expansion module
6EP4437-8XB00-0CY0
4
24 V
3%
0.2%
0.1 %
100 mV