Engineering and remote access
7.6 Cyclic and acyclic data
Data
Channel1 Utarget
[10mV]
Channel1 Ilimit
[10 mA]
Channel1 Ithreshold
(0-100%)
Fill byte(s)
Channel1 output
voltage [10mV]
Channel1 output
current [10mA]
Channel1 max output
current [10mA]
Channel1 Operation
mode
Channel1 operation
state
194
Description
Currently set setpoint of the output voltage for output 1.
Response threshold of the output current for output 1. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
-
Output voltage at output 1
Current at output 1
Maximum output current at output 1
Operating mode output 1:
If the actual load current
of an output exceeds the
specified response
threshold value of the
output current, then the
output can be shut down
according to a current-
time characteristic
(ELECTRONIC
SHUTDOWN), or the load
current can be limited to
the response threshold
(CONSTANT CURRENT).
Operating state output 1
4 = Running
The expansion module is
operating in the normal
mode.
5 = Buffering
Primary supply voltage
has failed. The expansion
module is operating in the
buffer mode.
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
1 = ModeModular
Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
0 = ManualOff
Output switched off man-
ually (button):
1 = RemoteOff
Output switched off
(PROFINET/IE):
2 = BufferOff
Output switched off
3 = OverLoadOff
Output switched off (over-
load):
4 = ReadyForRestart
Output ready for reset
(reset):
5 = ErrorOff
Output switched off (fault)
6 = Boot
Output switched off (pow-
ering up)
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76