Index 64: Identification values (reading/writing)
Data
Contact
Location
7.6.2.3

Data sets SITOP CNX8600

Index 1: Channel1...4 remote target values (reading/writing)
The saved data of an output are listed in the table below. The data applies to outputs 1 to 4.
Data
Utarget [10mV]
Ilimit [10mA]
Ithreshold (0-100%)
OutputEnable (0/255)
Reset
Operation Mode
Startup Delay [ms]
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Description
Currently set setpoint of the output voltage.
Response threshold of the output current for an output. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
Switch on output Switches the output on or off. A possible automatic shutdown
due to overload or power failure is not taken into account.
Resets the output: Resets the automatic overload shutdown of an output. As-
suming that the output is not switched off elsewhere, then after the reset, it is
switched on again.
Mode: If the actual load
current of an output ex-
ceeds the specified re-
sponse threshold value of
the output current, then
the output can be shut
down according to a cur-
rent-time characteristic
(ELECTRONIC
SHUTDOWN), or the load
current can be limited to
the response threshold
(CONSTANT CURRENT).
ON delay Individual delay time for the output, referred to a common starting
point. Only valid for system switch-on behavior "Variable on delay".
Description
Name of the contact person. You can change the
name to suit your requirements.
Location designation: Indicates the unique location
of the SITOP PSU8600.
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
1 = ModeModular
Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
Engineering and remote access
7.6 Cyclic and acyclic data
Data type
VisibleString(64)
VisibleString(44)
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned16
191