7.8.6.20
Web server
Display name
WebserverAutoLogoutEnableSet-
point
WebserverAutoReloadEnableSet-
point
WebserverEnableSetpoint
WebserverHttpAccessEnableSet-
point
WebserverReloadTimeSetpoint
7.8.6.21
Other
These nodes are listed at the first level in the object tree
Display name
DeviceManual
DeviceRevision
Hardware Revision
Manufacturer
Model
ModuleIdentNumber
OrderNumber
RevisionCounter
SerialNumber
SoftwareRevision
7.8.7
OPC UA - performance
OPC UA provides the option of collectively transferring modified actual values in the form of
a subscription. The minimum pole interval of such a subscription is 100 ms. A maximum of
150 data nodes can be simultaneously monitored, independent of whether these data nodes
are assigned one or various subscriptions.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Data type
Definition
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Byte
MultiStateValueDis-
creteType
Data type
Definition
String
PropertyType
String
PropertyType
String
PropertyType
LocalizedText
PropertyType
LocalizedText
PropertyType
LocalizedText
PropertyType
String
PropertyType
UInt32
PropertyType
String
PropertyType
String
PropertyType
Engineering and remote access
7.8 OPC UA server
Description
Log off automatically after 15
minutes
Activate automatic update.
Activate web server on this mod-
ule.
Permit access with HTTPS only.
Update interval
Description
Address (path in the file system or
URL/web address) of the operating
instructions for the device.
Revision status of the device hard-
ware
Name of the company that manu-
factured the device
Incremental counter that specifies
how often the static data in the
device was modified.
ID, which uniquely identifies the
device for the device manufacturer
Revision status of the device soft-
ware
261