Siemens PSU8600 Manual page 279

Sitop power supply
Hide thumbs Also See for PSU8600:
Table of Contents

Advertisement

ID
Severity
34
F
63
MR
61
N
62
N
90
MR
17
F
18
F
19
F
Alarm list SITOP CNX8600
ID
Severity
0
F
48
F
49
MD
50
MR
55
F
52
F
53
MD
54
MR
46
F
51
F
56
N
58
N
1
F
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Event
Safety shutdown of the output.
Buffer readiness disabled
Buffer mode
Sufficient buffer readiness
Output 1 interruption: Shutdown
initiated
Faulty communication to the mod-
ule.
Internal communication error
Internal communication error
Event
Incorrect checksum.
Critical error
Critical error
General error.
Hardware failure
Stored module configuration cor-
rupt
Stored module configuration cor-
rupt
Stored module configuration cor-
rupt
Invalid internal supply voltage.
Performing firmware update.
Different firmware version detected Different firmware version detected
Different serial number detected
Output switched off due to over-
heating.
Help text
A critical error occurred. This output of the power supply
system has been shut down.
No buffering possible because the buffer component has
been disabled.
The primary power supply has failed; the power supply
system is being supplied through the buffer component.
Sufficient buffer readiness has been achieved; the charge
status of the buffer components in the system has reached
the preset threshold value.
The shutdown of output 1 has been initiated in the course of
the output 1 interruption sequence.
Communication with the expansion module is faulty. All
outputs on the expansion module have been switched off.
A communication problem exists between primary and sec-
ondary side controllers. All outputs of the power supply
system have been switched off.
A communication problem exists between PROFINET mod-
ule and main controller.
Help text
Defective firmware detected. Device must be reactivated
with a new firmware update.
A critical error occurred. All outputs of the power supply
(module/system) have been shut down.
General critical error occurred. The device may therefore
behave inconsistently.
General error occurred. Device behavior remains consistent,
however.
A hardware failure has occurred. All outputs of the power
supply system have been switched off.
Stored module configuration is corrupt. The module cannot
start up correctly.
Stored module configuration is corrupt. Deviating module
behavior may be possible.
Stored module configuration is corrupt. Module behavior
remains consistent, however.
Voltage of the internal supply is too high. All outputs of the
power supply system have been switched off.
Performing firmware update. Read/write access is currently
not possible.
Different serial number detected
Overheating was detected at the output. The output has
been switched off.