7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals with one another
Test (C)
● Connect the output terminals with one another and measure against PE
Table 7- 1
Test voltages for 6EP1333-3BA10 and 6EP1334-3BA10
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
52
Test voltage diagram
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
4200 V DC
1 s
3000 V AC
1 s
2200 V DC
1 s
1500 V AC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 V DC
700 V DC
1500 V AC
500 V AC
4200 V DC
500 V DC
3000 V AC
350 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
Manual, 04.2018, C98130-A7548-A1-4-7629