States of the individual LEDs
①
Table 2- 4
"OK" LED
Signaling
Off
Green
Flashing green (1/1)
Flashing green (0.25/0.25)
Red
Flashing red (0.25/0.25)
Yellow
Flashing yellow (0.25/0.25)
Alternating, green/red
(0.25/0.25)
Table 2- 5
LED "MAN"
Signaling
Off
Green
Flashing green (1/1)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Device is OFF or is powering up (booting)
Normal operation
Phase asymmetry or phase failure
Detection from:
approx. 50 % rated load for 6EP3437-8MB00-2CY0
•
approx. 75 % rated load for 6EP3436-8MB00-2CY0
•
Operation with rated load is permissible for approx. 10 min.
System overload in normal operation:
Total output power in the range 101 - 150 %
Operation is permissible for 5 s/min
ERROR OFF: Device has automatically shut down as a result of device over-
•
temperature, phase dissymmetry, system overload
Internal device fault
•
Device ready for the automatic ERROR OFF shutdown to be reset – or after
•
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
Incorrect hardware configuration (REMOTE operating mode)
•
Power failure, buffer operation active
System overload in buffer operation: Total output power in the range
101 ... 150 % (operation is permissible for 5 s/min)
Firmware being updated
②
Device is OFF or is powering up (booting)
•
REMOTE mode, i.e. parameterization and remote control via PROFINET or
•
web server
MANUAL mode, i.e. setting directly at the device
MANUAL mode; the mode has been changed in operation, settings directly at
the device do not necessarily correspond to the active reference parameters.
Description, device design, dimension drawing
2.6 Displays