Siemens PSU8600 Manual page 267

Sitop power supply
Hide thumbs Also See for PSU8600:
Table of Contents

Advertisement

Index 49: PROFIenergy channel list (reading/writing)
Data
ChannelsOffList
Index 53: Web server settings (reading/writing)
Data
Activate web server on this module
Enable automatic update
Update interval
Enable automatic logoff
Permit access only with HTTPS
Padding
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
7.10 Parameter write behavior of the SITOP PSU8600
Description
Overview of the outputs that are shutdown. Each
output is represented using 1 bit (starting with bit 0
for output 1).
Description
Activating/deactivating the web server of the
SITOP PSU8600:
0: disable
255: enable
Activate/deactivate automatic update:
0: disable
255: enable
Update interval:
0: Off
5: 5 s
10: 10 s
20: 20 s
30: 30 s
60: 60 s
Activate/deactivate automatic logoff:
0: disable
255: enable
When automatic logoff is activated, the logged on
user ("Guest" or "Admin") is automatically logged
off when the SITOP PSU8600 web server is inac-
tive for 15 minutes.
Disable/enable access only via HTTPS
Fill byte(s)
Engineering and remote access
Data type
Unsigned32
Data type
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8