Engineering and remote access
7.8 OPC UA server
Display name
Alarm_F_Systemoverload
Alarm_F_SystemParametersCorrup
Alarm_F_UnexpectedEmptySlotDetected Boolean
Alarm_F_UnknownModuleDetected
Alarm_F_UzkHigh
AlarmF_WrongChecksum
Alarm_F_WrongExtensionModuleNumber Boolean
Alarm_F_SystemOverloadOutOfProfile
Alarm_F_SystemOverloadPeakload
Alarm_F_SafetyShutdownLoadCheck
Alarm_F_SafetyErrorOffLoadCheck
Alarm_F_RestartAfterCriticalCurrent
Alarm_F_RestartAfterPeakload
Alarm_MD_DeviceOvertemperature
Alarm_MD_General
Alarm_MD_LessCapableModuleDetected
244
Data type
Definition
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Description
System load current is outside the
permissible overload profile. Out-
puts of all expansion modules have
been switched off.
System configuration is incorrect.
Normal operation of the system is
not possible.
Unexpected empty slot detected
Unknown module found
Voltage of the internal supply is too
high. All outputs of the power sup-
ply system have been switched off.
Defective firmware detected. De-
vice must be reactivated with a
new firmware update.
Invalid number of modules detect-
ed. Invalid slot.
System load current is outside the
permissible overload profile. Out-
puts of all expansion modules have
been switched off.
System load current is outside the
permissible overload profile. Out-
puts of all expansion modules have
been switched off.
Critical load difference between the
AC input and the outputs. The
initiated safety shutdown will turn
off the device immediately.
Out of range difference between
AC input and outputs. Turn power
off and on to reactivate the system.
Ready for restart after safety shut-
down because of critical load cur-
rent. Turn power off and on to
reactivate the system.
Ready for restart after safety shut-
down because out of profile peak
load.
Danger of overtemperature detect-
ed in a system component. Imme-
diate load reduction is
recommended.
General critical error occurred. The
device may therefore behave in-
consistently.
A module with reduced power was
detected. Deviating system behav-
ior may be possible.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76