Index 7: Hardware settings (reading)
Data
Man/remote DipSwitch (0/255)
Priority Bufferd Channel 1 DipSwitch (0/255)
Startup Mode DipSwitch – Combination (0-3)
Operating Mode DipSwitch (0/255)
Soft Output Characteristics Output 1 (0/255)
Reserved DipSwitch 7 (0/255)
Webserver Enable DipSwitch (0/255)
Reset_In-Input (0/255)
Utarget Potentiometer [10mV]
Ilimit potentiometer [mA]
Output Enable manual button (0/255)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Description
Actual position of the operating selection switch at
the basic device SITOP PSU8600:
0 = "MANUAL" mode
255 = "REMOTE" mode
Actual switch position for prioritized buffering
(PRIO) of output 1 at the basic device
SITOP PSU8600.
Actual switch position for the system switch-on
behavior.
Actual switch position for the mode of output 4 at
the basic device SITOP PSU8600:
0 = constant current
255 = electronic shutdown
Soft output characteristic of output 1 of the
SITOP PSU8600 is activated.
Status of the reserved (unassigned) selector
switch 7.
Actual switch position for activating/deactivating
the web server.
0 = web server deactivated
255 = web server activated
Status of input "Reset_In": This input resets all
active faults and reactivates all of the outputs that
are in the "Ready for restart" operating state.
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
The response threshold is set in the following
steps depending on the maximum output current:
Output current 20 A: 20 mA (0.02 A)
Output current 40 A: 40 mA (0.04 A)
Values that deviate from this grid are rounded off
to the next permissible value in the device.
Actual DIP switch state for output 1:
0 = Manually shut down
255 = Manually switched on
Engineering and remote access
7.6 Cyclic and acyclic data
Data type
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8