Parameters For Setting Communication Via Bacnet - Siemens SINAMICS G110M Function Manual

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

5.5.1.1

Parameters for setting communication via BACnet

General settings
Processing times
p2024[0]: 0 ms ... 10000 ms, maximum processing time (APDU timeout), factory setting =
1000 ms,
p2024[1 ... 2]: Irrelevant
BACnet communication parameter
● p2025 [0]: 0 ... 4194303: Device object instance number,
Factory setting = 1
● p2025 [1]: 1 ... 10:
● p2025 [2]: 0 ... 39:
factory setting = 3
● p2025 [3]: 1 ... 127: Maximum Master address, factory setting = 127
Setting the COV_Increments
(COV = change of values) 0 ... 4194303.000, factory setting = 1. A maximum of 32 COVs
are permissible.
COV_Increment: Changes the value of the "present value" of an object instance for which
the server transfers an UnConfirmedCOV_Notification or ConfirmedCOV_Notification.
You can use these parameters to set for which inverter value changes an
UnConfirmedCOV_Notification or ConfirmedCOV_Notification result is sent.
The factory setting 1 means that the inverter sends an UnConfirmedCOV_Notification or
ConfirmedCOV_Notification if the considered value, e.g. for a range of 0 ... 10 V, changes by
an absolute value ≥ 1.
This requires an active SubscribeCOV_Service to send the relevant object instance.
You can also set the COV_Increment via the object property "COV_Increment" of the
relevant analog input, analog output or analog value.
BACnet language selection
German/English - only becomes effective after power off/on
Fieldbus error statistics
Displaying receive errors at the fieldbus interface
Fieldbuses
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
p2024[0 ... 2]
p2025[0 ... 3]
Maximum Info Frames, factory setting = 1
Number of APDU Retries (repeated attempts after fault telegrams),
p2026[0 ... 74]
p2027
r2029
Communication via RS485