8.10.7
Commissioning
8.10.7.1
Commissioning tool
We strongly recommend that you commission the safety functions using the STARTER PC
tool.
Table 8- 39
Download
STARTER
(http://support.automation.siemens.com/WW/vi
ew/en/10804985/130000)
8.10.7.2
Resetting the safety function parameters to the factory setting
Proceed as follows if you wish to reset the safety function parameters to the factory setting,
without influencing the standard parameters:
● Go online with STARTER.
● Open the screen form of the safety functions.
● Click on the "Restore Safety factory settings" button.
● Enter the password,for the safety functions.
● Confirm that the parameters have been saved (RAM to ROM).
● Go offline with STARTER.
● Switch off the converter supply voltage.
● Wait until all LEDs on the converter go dark. Now switch on the converter power supply
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
STARTER commissioning tool (PC software)
again (power on reset).
8.10 Fail-safe function Safe Torque Off (STO)
Order number
PC Connection Kit
The kit contains a STARTER DVD and USB cable
6SL3255-0AA00-2CA0
Functions
235