Fault rectification
6

Alarms and faults

6.3
Number
Cause
A01028
Configuration error
A01098
The power supply for the Control Unit
was interrupted for a longer period.
A01590
Motor maintenance interval lapsed
A01900
PROFIBUS: Configuration telegram
faulty
A01910
Setpoint timeout: p2040 ≠ 0 ms and
one of the following causes:
F01910
The bus connection is interrupted
The MODBUS master is switched
off
Communications error (CRC,
parity bit, logical error)
A01920
PROFIBUS: Cyclic connection
interrupt
A03520
Temperature sensor fault
A05000
Power Module overtemperature
A05001
A05002
A05004
A05006
A07012
I2t motor model overtemperature
A07015
Motor temperature sensor alarm
A07321
Automatic restart active
48
Siemens AG
LED
RDY
BF
Red – Fast
Red – Fast
Green - On
On
Green - On
Red – Slow
Green - On
Red – Fast
Alarms and faults
This is only an extract. The complete list of alarms and faults can be found in List
Manual CU230P (A5E02297932A AE).
Alarms
Solution
Parameterization on the memory card has been created with a different type of
module (order number, MLFB).
Check the module parameters and recommission if necessary.
Set the date and time of day of the real-time clock: p8400 (RTC time), p8401
(RTC date)
Deactivate the alarm: p8405 = 0.
Carry out maintenance and reset the maintenance interval (p0651).
A PROFIBUS master is attempting to establish a connection with a faulty
configuration telegram.
Check the bus configuration on the master and slave side.
Establish the bus connection and switch on the communication partners.
Possibly adapt p2040.
Set the PROFIBUS master to RUN.
The cyclic connection to the PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master with
cyclic operation.
Check that the sensor is correctly connected.
Check that the ambient temperature is within the defined limit values.
Check that the load conditions and duty cycle are appropriately dimensioned.
Check whether there has been a cooling system failure.
Reduce the motor load.
Check the ambient temperature and the motor ventilation.
Check the thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is correctly connected.
Check the parameter assignment (p0601).
Automatic restart is active. During voltage recovery or when remedying the causes
of pending faults, the drive is automatically switched back on.
Block the automatic restart (p1210 = 0).
Abort the restart process by removing the switch-on command (p8040).
Description
Incorrect memory card
Receive process data
Bus active - no process data
No bus activity
CM2G5111en
2014-05-16