Chapter 5 PLC Hardware Configuration (Primary PLC)

5.1

LC Reference Memory Settings

In the Hardware Configuration (Primary) double-click on the RX3i CPU module to display the configuration
settings. Click on the Memory tab and adjust the upper memory limits. The minimum settings are shown
below:
%AI Analog Input
%AQ Analog Output
%R Register Memory
%W Bulk Memory
Symbolic Discrete
Symbolic Non-Discrete
I/O Discrete
I/O Non-Discrete
5.2

Transfer List Entries

Input Transfer Points

%I
configured for length=0
%Q
(as needed)
%M
(as needed)
%G
(as needed)
%AI
configured for length=0
%AQ
(as needed)
%R
(as needed)
%W
(as needed)

Output Transfer Points

%I
configured for length=0
%Q
typically configured to the highest reference used for physical outputs, as a minimum
%M
(as needed)
%G
(as needed)
%AI
configured for length=0
%AQ
typically configured to the highest reference used for physical outputs, as a minimum
%R
(as needed)
%W
(as needed)
GFK-2928
16384
8192
32640
65536
65536
65536
65536
65536