Functions
2.11 Monitoring Functions

2.11.2.3 Settings

Addr.
Parameter
8201
FCT 74TC
8202
Alarm Delay

2.11.2.4 Information List

No.
Information
6851
>BLOCK 74TC
6852
>74TC trip rel.
6853
>74TC brk rel.
6861
74TC OFF
6862
74TC BLOCKED
6863
74TC ACTIVE
6864
74TC ProgFail
6865
74TC Trip cir.
2.11.3

Malfunction Responses of the Monitoring Functions

In the following malfunction responses of monitoring equipment are clearly listed.

2.11.3.1 Description

Malfunction Responses
Depending on the type of malfunction discovered, an annunciation is sent, a restart of the processor system is
initiated, or the device is taken out of service. After three unsuccessful restart attempts, the device is taken out
of service. The operational readiness NC contact operates to indicate the device is malfunctioning. Also, the
red LED "ERROR" lights up on the front cover, if the internal auxiliary voltage is present, and the green "RUN"
LED goes out. If the internal auxiliary voltage fails, all LEDs are dark. Table 2-14 provides a summary of the
monitoring functions and the malfunction responses of the relay.
216
Setting Options
ON
OFF
1 .. 30 sec
Type of In-
formation
SP
>BLOCK 74TC
SP
>74TC Trip circuit superv.: trip relay
SP
>74TC Trip circuit superv.: bkr relay
OUT
74TC Trip circuit supervision OFF
OUT
74TC Trip circuit supervision is BLOCKED
OUT
74TC Trip circuit supervision is ACTIVE
OUT
74TC blocked. Bin. input is not set
OUT
74TC Failure Trip Circuit
Default Setting
ON
74TC TRIP Circuit Supervision
2 sec
Delay Time for alarm
Comments
C53000-G1140-C207-2, Release date 01.2008
Comments
SIPROTEC, 7SJ62/64, Manual