Restart Inhibit for Motors (ANSI 66, 49Rotor)

General

2.33.1 Functional Description

Determining the
Rotor
Overtemperature
7UM62 Manual
C53000-G1176-C149-3
The rotor temperature of a motor generally remains well below its maximum allowable
temperature during normal operation and even during severe loading conditions.
However, during motor starting, the rotor can heat up quickly. If multiple starting
attempts are made in a short duration of time, the rotor could suffer thermal damage.
Therefore, the 7UM62 motor start blocking feature is available. A motor restart inhibit
signal is initiated when the relay projects rotor temperature exceeds the maximum
allowable temperature, and blocking continues until the calculated rotor temperature
decreases below the reset level. To block starting, the restart inhibit signal must be
masked to an output relay whose contact is inserted in the motor starting circuit.
Because the rotor current cannot be measured directly, the stator current must be
used to generate a thermal profile of the rotor. The r.m.s. values of the currents are
generated for this. The excessive rotor temperature Θ
of the three phase currents. The thermal limit values for the rotor winding are based
on manufacturer's data regarding the nominal starting current, maximum permissible
starting time, and the number of starts permitted from cold (n
conditions. From this data, the device performs the necessary calculations to establish
the thermal rotor profile and issues a blocking signal until the thermal rotor profile
decreases below the restarting limit.
Θ
L
Maximum permissible rotor temperature
Temperature curve:
Rotor cage bar
upper side limit
Rotor cage bar
lower side limit
Thermal
profile
1.
Startup
Rotor
Motor started
temper.
equilibr.
time
Current
CB I >
Figure 2-104Temperature Curve at the Rotor and the Thermal Profile during Repeated Start-
Up Attempts
Restart Inhibit for Motors (ANSI 66, 49Rotor)
2.
Startup
Startup
Rotor
Motor started
temper.
equilibr.
time
is calculated using the highest
R
) and warm (n
cold
τ
τ
·
Cool down at
k
at running
Cool down at
τ
τ
·
k
at stop
Threshold of restart
inhibit (ΘReInhib)
3.
Rotor
Motor started
temper.
equilibr.
time
)
warm
t
t
217

Advertisement

Table of Contents
loading

Table of Contents