AGC
There are three VDO inputs in the unit. The inputs have different functions, as the hardware
design allows for several VDO types.
VDO input 104: Oil pressure
VDO input 105: Cooling water temperature
VDO input 106: Fuel level sensor
VDO input 104
This VDO input is used for measuring the lubricating oil pressure.
VDO sensor type
Pressure
Type 1
Bar
0
10.0
0.5
27.2
1.0
44.9
1.5
62.9
2.0
81.0
2.5
99.2
3.0
117.1
3.5
134.7
4.0
151.9
4.5
168.3
5.0
184.0
6.0
7.0
8.0
9.0
10.0
The configurable type is configurable with 8 points.
Level switch type
Resistance
>200 Ω
<200 Ω
If the VDO input is used as a level switch, then be aware that no voltage must be
connected to the input. If any voltage is applied to the VDO inputs, then it will be
damaged. Refer to the Application Notes for further wiring information.
DEIF A/S

VDO inputs

Type 2
10.0
31.3
51.5
71.0
89.6
107.3
124.3
140.4
155.7
170.2
184.0
VDO sensor type
Type level switch
Function
Normal situation, no alarm
Alarm situation
Designer's Reference Handbook
Type configurable
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6
Point 7
Point 8
Page 103 of 168