4390 Wire Failure Analogue Input - Deif Multi-line 2 Designers Reference Handbook

Automatic gen-set controller/gs
Hide thumbs Also See for Multi-line 2:
Table of Contents

Advertisement

AGC
VDO input 105
This VDO input is used for measuring the cooling water temperature.
VDO sensor
type
Temperature
Type 1
°C
40
291.5
50
197.3
60
134.0
70
97.1
80
70.1
90
51.2
100
38.5
110
29.1
120
22.4
130
140
150
The configurable type is configurable with 8 points.
Level switch type
Resistance
<1.7k Ω
>1.7k Ω
If the VDO input is used as a level switch, then be aware that no voltage must be
connected to the input. If any voltage is applied to the VDO inputs, then it will be
damaged. Refer to the Application Notes for further wiring information.
VDO input 106
This VDO input is used for the fuel level sensor.
Value
0%
100%
Value
0%
100%
If the VDO input is used as a level switch, then be aware that no voltage must be
connected to the input. If any voltage is applied to the VDO inputs, then it will be
damaged. Refer to the Application Notes for further wiring information.
DEIF A/S
Type 2
Type 3
480.7
69.3
323.6
222.5
36.0
157.1
113.2
19.8
83.2
62.4
11.7
47.6
36.8
7.4
28.9
22.8
18.2
VDO sensor type
Type 3
Function
Normal situation, no alarm
Alarm situation
VDO sensor type
Type 1
Resistance
78.8 Ω
1.6 Ω
VDO sensor type
Type 2
Resistance
3 Ω
180 Ω
Designer's Reference Handbook
Type 4
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6
Point 7
Point 8
Page 104 of 168