Wiring Diagram; Digital Inputs - Deif CGC 200 Installation And Commissioning Instructions

Compact genset controller
Hide thumbs Also See for CGC 200:
Table of Contents

Advertisement

CGC 200 installation and commissioning
Installation
instructions 4189340806 UK

2.2.2 Wiring diagram

A wiring diagram for a typical installation is given below. Your system's wiring diagram may be different to the
diagram given below, since a different configuration may have been chosen.
Fuses
Fuses must be used to protect the controller. The auxiliary supply (DC) fuse rating must not be more than 2
A. The Genset L (AC) fuse rating must not be more than 1 A.
Grounding
The ground (Aux. supply -) is common for digital inputs. On the diagram below, the wiring drawn in the con-
troller box is internal wiring (this wiring is part of controller, and therefore not connected externally).
Connect the wiring according to the designer's wiring diagram for your system.

2.2.3 Digital inputs

All digital inputs are 12 or 24 V
optocouplers. The typical wiring is illustrated below:
dc
DEIF A/S
Page 7 of 32

Advertisement

Table of Contents
loading