Function inputs such as running feedback, remote start or access lock are never
inhibited. Only alarm inputs can be inhibited.
If an alarm is configured to activate a limit relay the relay will activate despite
that the inhibit input is ON.
Automatic RUN status
Alarms can be adjusted to activate only when the running feedback is active and a specific time
delay has expired.
The diagram below illustrates that after activation of the running feedback, a run status delay will
expire. When the delay expires, alarms with RUN status will be activated.
Run. feedback
DEIF A/S
Alarm inhibit input 23
Input ON
Input OFF
Active
-
Active
-
Active
-
t
RUN
Alarms active
Designer's Reference Handbook
Comment
Digital inputs
Digital inputs
4-20mA inputs
t
Page 72 of 168