Battery Test - Deif Multi-line 2 Designers Reference Handbook

Automatic gen-set controller/gs
Hide thumbs Also See for Multi-line 2:
Table of Contents

Advertisement

AGC
This function gives the possibility to test the condition of the battery. The battery test initiates
with a digital input and is available when the gen-set is in semi-auto mode.
If a mains failure occurs during the battery test sequence, the test will automatically be
interrupted, and the automatic mains failure start up sequence will be activated.
During the test the battery voltage will decrease, and an alarm will occur if it drops to the
setpoint.
U
BATTERY
Alarm
Test 1
The drawing shows that test #1 is carried out without a large voltage drop of the battery voltage,
whereas test #2 reaches the alarm setpoint.
As there is no reason to wear the battery down even more, the test stops when the battery test
alarm occurs.
The test is typically used at periodical intervals, e.g. once every week. The engine must be at a
standstill when the test is started. Otherwise, the test command will be ignored.
The stop relay will act depending on the coil type selection in 6210 Stop
:
Stop coil:
Run coil:
DEIF A/S

Battery test

t
BAT TEST
The stop relay activates during the test.
The stop relay stays deactivated during the test.
Designer's Reference Handbook
t
BAT TEST
Cancel test
Test 2
t
Page 92 of 168

Advertisement

Table of Contents
loading