AGC
The conditions for the ON and OFF sequences are described in the table below:
Conditions for breaker operations
Sequence
GB ON, direct closing
MB ON, direct closing
GB ON, synchronising
MB ON, synchronising
GB OFF, direct opening
MB OFF, direct opening
GB OFF, deloading
MB OFF, deloading
When the breakers open and they need to reclose immediately, then the
adjustable timer 6252 GB load time or 6615 MB load time must expire before
closing is possible. This is the time the breaker uses to reload the spring.
If the digital inputs 'MB spring loaded' and 'GB spring loaded' are configured,
then they must be activated before the breakers can close.
DEIF A/S
Designer's Reference Handbook
Condition
Running feedback
Generator frequency/voltage OK
MB open
Mains frequency/voltage OK
GB open
Running feedback
Generator frequency/voltage OK
MB closed
No generator failure alarms
Mains frequency/voltage OK
GB closed
No generator failure alarms
MB open
Alarms with fail classes:
Shut down
Trip GB alarms
MB closed
Alarms with fail classes:
Trip and stop
Page 50 of 168
Need help?