AGC
In chapter 10 each parameter description is structured according to the same principles. Under the
parameter title heading, the detailed parameter descriptions are illustrated and presented. First, a
table indicating the parameter facts related to the individual parameter title is presented:
Menu
Parameter
number
title and
indicated
menu
in display
number
1010 Reverse power
No.
Setting
1011
Reverse power
1012
Reverse power
1013
Reverse power
1014
Reverse power
1015
Reverse power
1016
Reverse power
Small differences due to the character of the parameters may exist between the
individual tables.
The first column indicates the menu number in the display.
The second column indicates the changeable setting in the display.
The third and fourth columns indicate the minimum/maximum setpoint available for this setting.
The sixth column indicates the default setpoint of the unit from the factory. When it is necessary,
additional information will be supplied after the table in order to make the individual parameter
descriptions as informative as possible.
At this point of the process you will have located the specific parameter description that you were
looking for. Now, follow the menu structure presented earlier in this handbook in order to set up the
individual parameters. (In this overall example we have chosen to change the setpoint of the
parameter 1010 Reverse power ).
Step 1:
Enter the 'setup' menu via SETUP in the fourth display line in the entry window
Step 2:
Enter the 'protection' menu via PROT in the fourth display line in the setup menu
Step 3:
Enter the 'setpoint 1' menu via PROT1 in the fourth display line in the setup menu
Step 4:
Use JUMP or the
Step 5:
Enter the 'setpoint' menu via LIM in the fourth display line
Step 6:
Enter password to change the setpoint
Step 7:
Use the
Step 8:
Use the 'underscore' to save the new setpoint setting
DEIF A/S

Parameter descriptions

Changeable
settings
indicated in
display
Min.
setting
Setpoint
-50.0%
Timer
0.1 s
Relay output A
R0 (none)
Relay output B
R0 (none)
Enable
OFF
Fail class
1

Setup

and
push-buttons to locate the selected parameter
and
push-buttons to increase/decrease the setpoint setting
Designer's Reference Handbook
Min. – max.
setpoints
Max.
Third
setting
setting
0.0%
-
100.0 s
-
R3
-
(relay 3)
R3
-
(relay 3)
ON
RUN
5
-
Default setpoint
from factory
Factory
setting
-5.0%
10.0 s
R0 (none)
R0 (none)
ON
3
Page 145 of 168