AGC
No.
Setting
2081
MB general fail.
2082
MB general fail.
2083
MB general fail.
The general failure alarms cannot be disabled.

2090 Breaker failure alarms

The fail class of the breaker open and close failure alarms can be adjusted in this menu.
No.
Setting
2091
MB open failure
2092
MB close failure
2093
GB open failure
2094
GB close failure
See page 91 regarding fail class selection.

2100 Separate synchronisation relay

No.
Setting
2101
Generator breaker Relay output A
2102
Mains breaker

2110 Close before excitation

No.
Setting
2111
Close bf. excit.
2112
Close bf. excit.
2113
Close bf. excit.
2114
Close bf. excit.
2115
Close bf. excit.

2120 Breaker sequence

No.
Setting
2121
Breaker seq.
2122
Breaker seq.
2123
Breaker seq.

2130 Excitation failure

No.
Setting
2131
Excit. failure
2132
Excit. failure
2133
Excit. failure
2134
Excit. failure
2135
Excit. failure
DEIF A/S
Delay
Relay output A
Relay output B
Fail class
Fail class
Fail class
Fail class
Relay output B
Setpoint
Timer
Relay output A
Relay output B
Enable
Break
Timer
Run 90
Timer
Relay output A
Relay output B
Enable
Fail class
Designer's Reference Handbook
Min. setting
Max. setting
30.0 s
300.0 s
R0 (none)
Option
dependent
R0 (none)
Min. setting
Max. setting
1
6
1
6
1
6
1
6
Min. setting
Max. setting
R0 (none)
Option
dependent
R0 (none)
Min. setting
Max. setting
0 RPM
4000 RPM
0.0 s
999.0 s
R0 (none)
Option
R0 (none)
dependent
OFF
ON
Min. setting
Max. setting
Close GB
Close GB+TB Close GB
0.0 s
999.0 s
0 RPM
4000 RPM
Min. setting
Max. setting
0.0 s
999.0 s
R0 (none)
Option
dependent
R0 (none)
OFF
ON
Alarm (1)
Trip MB (6)
Factory
setting
60.0 s
R0 (none)
R0 (none)
Factory
setting
2 (warning)
2 (warning)
2 (warning)
2 (warning)
Factory
setting
R0 (none)
R0 (none)
Factory
setting
400 RPM
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
5.0 s
1450 RPM
Factory
setting
5.0 s
R0 (none)
R0 (none)
OFF
Warning (2)
Page 152 of 168