Analogue Inputs Used As Digital Inputs; Site Battery Inputs; Magnetic Pick-Up (Mpu) Input - Deif SGC 410 User Manual

Single genset controller
Table of Contents

Advertisement

3.8 Analogue inputs used as digital inputs

Analogue inputs can be used as digital inputs when wired as shown.
F1
+
8-32
V DC
-

3.9 Site battery inputs

Category
Controller terminals
Number of inputs
Type
Range
Resolution
Accuracy
Site battery run hours
In this feature, controller calculates the run hours for which the site runs on the battery backup. Site battery run hours are
incremented only when the genset contactors are not latched and when site battery voltage is greater than low battery voltage
threshold.

3.10 Magnetic pick-up (MPU) input

Category
Controller terminal
Measurement type
Frequency range
Input voltage range
The Magnetic pick-up (MPU) is an inductive sensor fitted on the engine flywheel for the engine speed sensing. The output of the
MPU is a sine-wave signal.
USER MANUAL 4189341243A UK
Specifications
24, 25
2
Differential
±60 V
0.1 V
±2 % of full scale
Specifications
22
Single ended
10 to 10 kHz
200 mV to 45 V AC RMS
Page 11 of 78