AGC
The configurable type is configurable with 8 points.
VDO usage
The VDO inputs are used as alarm inputs and can be configured in the following menus:
VDO input 104: Lubricating oil pressure – alarm settings in menus 4170/4180.
VDO input 105: Cooling water temperature – alarm settings in menus 4190/4200.
VDO input 106: Fuel level switch – alarm settings in menus 4210/4220.
DEIF A/S
VDO sensor
type
Value
Type
configurable
%
Resistance
0
Point 1
10
20
30
40
Point 2
50
Point 3
60
Point 4
70
Point 5
80
Point 6
90
Point 7
100
Point 8
Designer's Reference Handbook