Deif Multi-line 2 Designers Reference Handbook page 89

Automatic gen-set controller/gs
Hide thumbs Also See for Multi-line 2:
Table of Contents

Advertisement

AGC
Running signal
The running feedback must be activated when the gen-set is running in idle mode.
Idle speed flowcharts
The flowcharts illustrate the starting and stopping of the gen-set by use of the inputs 'temp
control' and 'low speed'.
Start
start the genset
DEIF A/S
Start
Auto
Yes
No
start/stop
ON
start the genset
low speed ON
Yes
Genset running
at idle speed
No
idle timer
idle timer ON
expired
Yes
genset running
Designer's Reference Handbook
No
temp control
No starting
ON
Yes
No
No
Yes
at f
NOM
END
Page 89 of 168