Event Log - Deif Multi-line 2 Designers Reference Handbook

Automatic gen-set controller/gs
Hide thumbs Also See for Multi-line 2:
Table of Contents

Advertisement

AGC
The event log holds up to 150 events, and they can be viewed in the display or in the PC utility
software. When more than 150 events have occurred, each new event will overwrite the oldest
event following the 'first in – first out' principle.
Display
In the display it looks like this when the 'LOG' push-button is pressed (example):
The specific alarm or event is shown in the second line. In the example above the fuel level
alarm has occurred. The third line shows the time stamp.
If the cursor is moved to 'INFO', the actual value can be read when pressing 'SEL':
The first event in the list will be displayed, if the cursor is placed below 'FIRST' and 'SEL' is
pressed.
The last event in the list will be displayed, if the cursor is placed below 'LAST' and 'SEL' is
pressed.
The keyUP and keyDOWN push-buttons are used for navigating in the list.
PC utility software
Using the PC utility software the entire log stack of the last 150 events can be retrieved by
activating the log button on the horizontal toolbar.
The alarms and events are displayed as indicated below. The actual alarms are displayed in the
text column together with selected measurements.
In the right side column additional data is indicated. This is specific data for the most important
measurements. The data is logged for each specific event and is used for troubleshooting after
each alarm.
DEIF A/S

Event log

G 400 400 400V
4170 Fuel level
06-24
15:24:10.3
INFO
FIRST L AST
G 400 400 400V
4170 Fuel level
VALUE
8 %
INFO
FIRST L AST