When the gen-set is running in semi-auto mode, the unit will control the speed governor and the
AVR, if option D1 is selected.
It is possible to manually increase and decrease the speed/voltage when semi-
auto is selected. When the digital up/down input is activated, then the regulator
is deactivated as long as the manual up/down inputs are activated.
Manual voltage control is option dependent (option D1).
The following sequences can be activated in semi-auto:
Command
Description
Start
The start sequence is initiated and continues until the gen-
set starts or the maximum number of start attempts has
been reached. The frequency (and voltage) will be
regulated to make the GB ready to close.
Stop
The gen-set will be stopped. After disappearance of the
running signal, the stop sequence will continue to be active
in the 'extended stop time' period. The gen-set is stopped
without cooling-down time.
Close GB
The unit will close the generator breaker, if the mains
breaker is open, synchronise and close the generator
breaker, if the mains breaker is closed.
Open GB
The unit will ramp down and open the generator breaker at
the breaker open point, if the mains breaker is closed. The
unit will open the generator breaker instantly, if the mains
breaker is open or the gen-set mode is island mode.
Close MB
The unit will close the mains breaker, if the generator
breaker is open, synchronise and close the mains breaker,
if the generator breaker is closed.
Open MB
The unit opens the mains breaker instantly.
Manual
The regulator is deactivated and the governor output is
GOV UP
activated as long as the GOV input is ON.
Manual
The regulator is deactivated and the governor output is
GOV DOWN
activated as long as the GOV input is ON.
Manual
The regulator is deactivated and the governor output is
AVR UP
activated as long as the AVR input is ON.
Manual
The regulator is deactivated and the governor output is
AVR DOWN
activated as long as the AVR input is ON.
General test mode description
The test mode function is activated by selecting test with the MODE push-button on the display
or by activating a digital input, if one of them is configured to 'test'. The test mode will only test
synchronising, if the 'Sync. to mains' function is enabled. If this is the case, the gen-set will start,
and the unit will synchronise and close the generator breaker to let the gen-set run in parallel,
until the test time expires. If the 'Sync. to mains' function is not activated, then the gen-set will
start and run at the nominal frequency with the generator breaker open.
DEIF A/S
Designer's Reference Handbook
Comment
When AMF mode
is
selected,
unit will not regu-
late after breaker
closure.
Option
D1
required.
Option
D1
required.
Page 20 of 168