6060 Gen-Set Modes; 6070 Date And Time (Internal Clock) Setting; 6080 Counters; 6090 Service Timer - Deif Multi-line 2 Designers Reference Handbook

Automatic gen-set controller/gs
Hide thumbs Also See for Multi-line 2:
Table of Contents

Advertisement

AGC

6060 Gen-set modes

No.
Setting
6061
Gen-set mode
Gen-set mode
Gen-set mode
Gen-set mode
Gen-set mode
Gen-set mode

6070 Date and time (internal clock) setting

The date and time can easily be synchronised with the present time and date
from the utility software.
No.
Setting
6071
Date and time
6072
Date and time
6073
Date and time
6074
Date and time
6075
Date and time
6076
Date and time

6080 Counters

The settings below (except kWh) are offset values that need to be adjusted at the
commissioning if the display is used for reading the values. A breaker operation is counted each
time the breaker closes.
The setting 'reset kWh counter' resets the value of the produced kWh.
No.
Setting
6081
Counters
6082
Counters
6083
Counters
6084
Counters
6085
Counters

6090 Service timer

The function of the service timer enables the user to get an alarm when service of the gen-set is
needed. The timer is reset when the alarm is acknowledged or when the timer is disabled and
enabled again.
No.
Setting
6091
Service timer
6092
Service timer
6093
Service timer
6094
Service timer
6095
Service timer
DEIF A/S
Island operation
AMF
Peak shaving
Fixed power
Mains power export
Load take over
Year
Month
Day
Weekday
Hour
Minute
Running time
GB operations
MB operations
kWh
Start attempts
Setpoint
Relay output A
Relay output B
Enable
Fail class
Designer's Reference Handbook
Setting
Island operation
AMF
Peak shaving
Fixed power
Mains power export
Load take over
Min. setting
Max. setting
2001
2100
1
12
1
31
1
7
0
23
0
59
Min. setting
Max. setting
0
20000
0
20000
0
20000
OFF
ON
0
20000
Min. setting
Max. setting
0 h
9000 h
R0 (none)
Option
R0 (none)
dependent
OFF
ON
Alarm (1)
Trip MB (6)
Factory
setting
-
AMF
-
-
-
-
Factory
setting
Depending on
the
software
version
Factory
setting
0
0
0
OFF
0
Factory
setting
500 h
R0 (none)
R0 (none)
ON
Warning (2)
Page 164 of 168