AGC
Illustration of configurable inputs
Resistance
(Ω)
Setpoint 8
Setpoint 7
Setpoint 6
Setpoint 5
Setpoint 4
Setpoint 3
Setpoint 2
Setpoint 1
Configuration
The 8 curve settings for the configurable VDO inputs cannot be changed in the display, but only
in the PC utility software. The alarm settings can be changed both in the display and in the PC
utility software. In the PC utility software the configurable inputs are adjusted in this dialog box:
Adjust the resistance of the VDO sensor at the specific measuring value. In the example above
the adjustment is 10 Ω at 0.0 bar.
DEIF A/S
1
2
3
4
5
Setpoints
Designer's Reference Handbook
6
7
8
Value
(bar, °C or %)
Page 106 of 168