Prepare to Install an Exalogic Machine
•
2: Width between the centers of the mounting hole slots is 374 mm (14.72
inches)
•
3: Distance between mounting bracket to the edge of the rack is 113 mm (4.45
inches)
•
4: Distance between the centers of the front and rear mounting hole slots is
1120 mm (44.1 inches)
•
5: Depth of cable-routing floor cutout is 330 mm (13 inches)
•
6: Distance between the floor cutout and the edge of the rack is 160 mm (6.3
inches)
•
7: Width of cable-routing floor cutout is 280 mm (11 inches)
If you plan to route data or PDU power cords down through the bottom of the
rack, then you need to cut a hole in the installation floor site. Cut a rectangular hole
below the rear portion of the rack, between the two rear casters and behind the rear
RETMA (Radio Electronics Television Manufacturers Association) rails.
shows the base positions of the rack from the bottom.
Figure 3-6
Caution:
Do not create a hole where the rack casters or leveling feet brackets will be
placed.
Open the front and rear Exalogic machine doors.
3.
3-10 Oracle Exalogic Elastic Cloud Machine Owner's Guide
Base Position to Measure
Figure 3-6