Electrical Power Requirements
Table 2-4
Table 2-4

PDU Requirements for Low Voltage

Specification
15 kVA, 1 ph
Phase
1 ph
Market Part
6442A
Number
Manufacturing
597-0566-01
Part Number
Voltage
200-240 VAC 1ph
Amps Per PDU
72A (3 × 24A)
Outlets
42 C13, 6 C19
Number of
3x30A, 1 ph
Inputs
Current
24A max. per
input
Data Center
NEMA L6-30R
Receptacle
Number of
6
Outlets Per Rack
Table 2-5
Table 2-5

PDU Requirements for High Voltage

Specification
15 kVA, 3 ph
Phase
3 ph
Market Part Number
6441A
Manufacturing Part
597-0565-01
Number
Voltage
220/380-240/415 VAC 3ph
Amps Per PDU
62.7 A (3 × 20.9A)
Outlets
42 C13, 6 C19
Number of Inputs
1x25A, 3 ph
2-4 Oracle Exalogic Elastic Cloud Machine Owner's Guide
lists the PDU low voltage requirements.
15 kVA, 3 ph
3 ph
6440A
597-0564-01
200-240 VAC 3ph
69A (3 × 23A)
42 C13, 6 C19
1x60A, 3 ph
40A max. per phase
IEC309-3P4W-IP67
(60A, 250V, AC, 3 ph)
IEC309 60A 3ph 4 Wire
Hubbell
HBL460R/C9W or
equivalent.
2
lists the PDU high voltage requirements.
22 kVA, 1 ph
1 ph
7100873
7018123
200-240 VAC 1ph
110.4 (3x36.8A)
42 C13, 6 C19
3 x50A 1 ph
36.8A per input
Hubbell CS8265C
6
22 kVA, 1 ph
1 ph
7100874
7018124
200-240 VAC 1ph
96A (3x32A)
42 C13, 6 C19
3 x 32A 1 ph
24 kVA, 3 ph
3 ph
XSR-24K-IEC309-4P
594-5596-01
200-240 VAC 3ph
120A (6 × 20A)
42 C13, 6 C19
2x60A, 3 ph
34.6A max. per phase
IEC309-3P4W-IP67
(60A, 250V, AC, 3 ph)
IEC309 60A 3ph 4
Wire
Hubbell
HBL460R/C9W or
equivalent.
4
24 kVA, 3 ph
3 ph
XSR-24K-IEC309-5P
594-5600-01
220/380-240/415 VAC
3ph
109A (6 × 18.1A)
42 C13, 6 C19
2x25A, 3 ph