Main Circuit Terminal Power Supply And Motor Wiring - YASKAWA T1000V Technical Manual

Ac drive for textile applications
Table of Contents

Advertisement

Model
CIMR-TC4V
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, –,
+1, +2, B1, B2
0018
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, –,
+1, +2
0023
B1, B2
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, –,
+1, +2
0031
B1, B2
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, –,
+1, +2
0038
B1, B2

◆ Main Circuit Terminal Power Supply and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor
terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor
should match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters
could result in damage to the drive.
NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious
injury by fire as a result of drive damage from line voltage application to output terminals.
Cable Length Between Drive and Motor
When the cable length between the drive and the motor is too long (especially at low frequency output), note that the
cable voltage drop may cause reduced motor torque. Drive output current will increase as the leakage current from the
cable increases. An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the
current detection.
Adjust the drive carrier frequency according to the following table. If the motor wiring distance exceeds 100 m because
of the system configuration, reduce the ground currents.
Refer to
Table 3.5
to set the carrier frequency to an appropriate level.
Cable Length
Carrier Frequency
Note: When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected motors when running
multiple motors from a single drive.
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Screw
Terminal
Table 3.5 Cable Length Between Drive and Motor
50 m or less
15 kHz or less
Tightening Torque
Size
N•m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
2 to 2.5
M5
(17.7 to 22.1)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
2 to 2.5
M5
(17.7 to 22.1)
2 to 2.5
M5
(17.7 to 22.1)
2 to 2.5
M5
(17.7 to 22.1)
4 to 6
M6
(35.4 to 53.1)
2 to 2.5
M5
(17.7 to 22.1)
2 to 2.5
M5
(17.7 to 22.1)
4 to 6
M6
(35.4 to 53.1)
Refer to C6-02: Carrier Frequency Selection on page
100 m or less
5 kHz or less
3.6 Main Circuit Wiring
Recommended
Applicable Gauge
Gauge
mm
2
(AWG)
mm
2.5 to 6
(14 to 10)
6 to 16
(10 to 6)
6 to 16
(10 to 6)
2.5 to 6
(14 to 10)
6 to 16
(10 to 6)
6 to 16
(10 to 6)
6 to 10
(10 to 8)
6 to 16
(10 to 6)
6 to 16
(10 to 6)
6 to 10
(10 to 8)
6 to 16
(10 to 6)
Greater than 100 m
2 kHz or less
(AWG)
2
6
(10)
6
(10)
10
(8)
6
(10)
6
(10)
10
(8)
10
(8)
10
(8)
10
(8)
10
(8)
10
(8)
3
141.
55