Operator Programming Errors; Operator Programming Errors; Operator Programming Error Codes, Causes, And Possible Solutions - YASKAWA A1000 Series Quick Start Manual

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

5.4

Operator Programming Errors

u

Operator Programming Error Codes, Causes, and Possible Solutions

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an
inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not
trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to
oPE02 or oPE08 appear on the operator display, press the ENTER button to view U1-18 and see which parameter is causing
the oPE.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Table 5.4 oPE Codes, Causes, and Possible Solutions
oPE01
oPE02
oPE03
oPE04
oPE05
oPE06
oPE07
oPE08
oPE09
oPE10
oPE11
oPE13
oPE15
oPE16
oPE18

5.4 Operator Programming Errors

Table 5.4
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-08.
Initialization Required
Run Command/Frequency Reference Source Selection Error
Control Method Selection Error
Correct the setting for the control method.
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,
H3-10, or H3-06 and PID functions conflict.
Parameter Selection Error
A function has been set that cannot be used in the motor control method
selected.
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is
enabled (b5-01 = 1 to 4).
V/f Data Setting Error
One or more of the parameters listed below are not set according to the
formula:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Pulse Monitor Selection Error
Incorrect setting of monitor selection for pulse train (H6-06).
Torque Control Setting Error
Parameter settings that are not allowed in combination with Torque Control
have been set.
Energy Savings Constants Error
Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.