Verifying And Backing Up Parameter Settings; Verifying And Backing Up Parameter Settings; Parameter Access Level: A1-01; Password Settings: A1-04, A1-05 - YASKAWA CIMR-JA Series Installation & Start-Up Manual

Compact v/f control drive
Hide thumbs Also See for CIMR-JA Series:
Table of Contents

Advertisement

4.9 Verifying and Backing Up Parameter Settings

4.9
Verifying and Backing Up Parameter
Settings
Check changes to parameter settings using the Verify function.
Changes: Verify Menu on page
Save the verified parameter settings. Change the access level or set a password to the drive to
prevent accidental modification of parameter settings.
u

Parameter Access Level: A1-01

Setting the Access Level for "Operation only" (A1-01 = 0) allows the user to access parameters
A1-oo and Uo-oo only. Other parameters are not displayed.
Parameter
No.
Name
Selects which parameters are accessible via the digital operator.
Access
0: Operation only (A1-01 and A1-04 can be set and monitored. U
A1-01
Level
parameters can be monitored)
Selection
2: Advanced Access Level (All parameters can be set and monitored)
u

Password Settings: A1-04, A1-05

The user can set a password to the drive to restrict access. The password is selected via
parameter A1-05. The selected password must be entered in parameter A1-04 to unlock
parameter access (i.e., parameter setting A1-04 must match the value programmed into
A1-05). The following parameters cannot be viewed or edited until the value programmed
into A1-04 correctly matches the value as programmed in parameter A1-05: A1-01, A1-02,
and A1-03.
Note:
Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously
depress the
116
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
83.
Description
key and the
key.
Refer to Verifying Parameter
Setting
Range
0,2
Default
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-jt seriesJ1000 series

Table of Contents