3.3 Main Circuit Connection Diagram

3.3

Main Circuit Connection Diagram

Refer to diagrams in this section for the Main Circuit wiring connections. Connections may vary based on drive capacity.
The main circuit DC power supply powers the control circuit.
NOTICE: Do not use the negative DC bus terminal "-" as a ground terminal. This terminal is at high voltage DC potential. Improper
wiring connections could result in damage to the drive.

◆ Single-Phase 200 V Class (CIMR-TCBV0001 to 0012)

Figure 3.3
NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may damage the drive.
◆ Three-Phase 200 V Class (CIMR-TC2V0001 to 0069);
Three-Phase 400 V Class (CIMR-TC4V0001 to 0038)
Figure 3.4
50
DC reactor
(option)
Jumper
+2
R/L1
S/L2
Single-phase
200 Vac
Figure 3.3 Connecting Single-Phase Main Circuit Terminals
Jumper
Three phase 200 Vac
(400 Vac)
Figure 3.4 Connecting Three-Phase Main Circuit Terminals
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Braking Resistor
Unit (option)
+1
B1 B2
Drive
U/T1
Motor
V/T2
W/T3
Braking
DC reactor
Resistor Unit
(option)
(option)
+2
+1
B1 B2
Drive
R/L1
U/T1
S/L2
V/T2
Motor
T/L3
W/T3