5.1 A: Initialization

5.1

A: Initialization

The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.

◆ A1: Initialization

A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No.
A1-00
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
A1-01
Setting 0: Operation Only
Access is restricted to parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, and all A2
parameters cannot be modified.
• If a digital input programmed for Program Lockout (H1-
even though the A1-01 is set to 1 or 2.
• If parameters are changed via serial communication the parameters can not be changed from the digital operator until
an Enter command is received from the serial communication.
A1-02: Control Mode Selection
Selects the Control Method of the drive.
Note: 1. Auto-Tuning must be performed on the motor when A1-02 = 2, 5.
2. This parameter is not reset when the drive is initialized using parameter A1-03.
No.
A1-02
Setting 0: V/f Control
• For general-purpose and multiple motor applications.
• For use when the motor parameters are unknown and Auto-tuning can not be performed.
102
Parameter Name
Language Selection
Parameter Name
Access Level Selection
Parameter Name
Control Method Selection
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting Range
0 to 7
Setting Range
0 to 9999
= 1B) is enabled, parameter values can not be modified,
Setting Range
0, 2, 5
Default
0
Default
2
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents