YASKAWA T1000V Technical Manual page 417

Ac drive for textile applications
Table of Contents

Advertisement

Use UL compliant fuses listed in the following table when wiring the main circuit. Branch circuit protection shall be
provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Exceptional models are A6T6 with 2V0002, A6T15 with 2V0004 or 4V0004, A6T20 with 4V0005, and A6T25 with 4V0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay Class-T
Drive Model CIMR-T
(Manufacturer: Ferraz)
BV0001
BV0002
BV0003
BV0006
BV0010
BV0012
2V0001
2V0002
2V0004
2V0006
2V0010
2V0012
2V0020
2V0030
2V0040
2V0056
2V0069
4V0001
4V0002
4V0004
4V0005
4V0007
4V0009
4V0011
4V0018
4V0023
4V0031
4V0038
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class
2 (UL regulations) power supply for the control circuit terminal.
Input / Output
Open Collector Outputs
Digital Inputs / Outputs
Analog Inputs / Outputs
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Table D.5 Recommended Input Fuse Selection
Fuse Type
Fuse Ampere Rating
600 Vac, 200 kAIR
Single-Phase 200 V Class
A6T6
A6T10
A6T20
A6T40
A6T40
A6T50
Three-Phase 200 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T30
A6T40
Not Available
Three-Phase 400 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T30
Not Available
Table D.6 Control Circuit Terminal Power Supply
Terminal Signal
P1, P2, PC
S1, S2, S3, S4, S5, S6, SC,
HC, H1, RP, MP
+V, A1, A2, AC, AM
Fuse Type
(Manufacturer: Bussmann)
(A)
500 Vac, 200 kAIR
6
FWH-25A14F
10
FWH-25A14F
20
FWH-60B
40
FWH-80B
40
FWH-100B
50
FWH-125B
3
FWH-25A14F
6
FWH-25A14F
15
FWH-25A14F
20
FWH-25A14F
25
FWH-70B
30
FWH-70B
40
FWH-90B
FWH-100B
FWH-200B
FWH-200B
FWH-200B
3
FWH-40B
6
FWH-40B
15
FWH-50B
20
FWH-70B
25
FWH-70B
25
FWH-90B
30
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
Power Supply Specifications
Requires class 2 power supply.
Use the internal LVLC power supply of the drive. Use class 2 for external
power supply.
Use the internal LVLC power supply of the drive. Use class 2 for external
power supply.
D.3 UL Standards
Fuse Ampere Rating
(A)
25
25
60
80
100
125
25
25
25
25
70
70
90
100
200
200
200
40
40
50
70
70
90
90
80
100
125
200
D
417

Hide quick links: