YASKAWA T1000V Technical Manual page 348

Ac drive for textile applications
Table of Contents

Advertisement

B.3 Parameter Table
No.
Name
L6-05
Torque Detection Level 2
<15>
L6-06
Torque Detection Time 2
<15>
L7-01
Forward Torque Limit
<15>
L7-02
Reverse Torque Limit
<15>
L7-03
Forward Regenerative
Torque Limit
<15>
L7-04
Reverse Regenerative
Torque Limit
<15>
L7-06
Torque Limit Integral Time
Constant
<15>
Torque Limit Control
L7-07
Method Selection during
Accel/Decel
Internal Dynamic Braking
L8-01
Resistor Protection
Selection (ERF type)
L8-02
Overheat Alarm Level
Overheat Pre-Alarm
L8-03
Operation Selection
Input Phase Loss Protection
L8-05
Selection
348
Description
Sets the overtorque/undertorque detection level. 100% is
equal to the motor rated current in V/f Control or PM OLV
and equal to the motor rated torque in Open Loop Vector
Control.
Sets the length of time an overtorque/undertorque
condition must exist before torque detection 2 is
recognized by the drive.
L7: Torque Limit
Use L7 parameters to configure the torque limit function.
Sets the torque limit value as a percentage of the motor
rated torque. Four individual quadrants can be set.
output torque
L7-04
regeneration
REV
regeneration
L7-02
Sets the integral time constant for the torque limit.
Selects the method of torque limit control during accel/
decel.
0: Proportional Control (change to integral controls at fixed
speeds). Use this setting when acceleration to the desired
speed has priority over torque limitation.
1: Integral Control. Use this setting if the torque limitation
has priority.
When torque limit is applied to the motor, accel/decel time
may increase and motor speed may not meet the speed
reference.
L8: Drive Protection
Use L8 parameters to configure hardware protection functions.
Selects the Braking resistor when using a 3% duty cycle
heatsink mounted braking resistor. This parameter does not
enable or disable the braking transistor of the drive.
0: Resistor overheat protection disabled
1: Resistor overheat protection enabled
Sets the temperature for the heatsink overheat alarm oH.
If the heatsink temperature exceeds the value set to L8-02,
an output terminal set for the oH alarm (H2-
close.
Determines the action the drive should take when the
heatsink overheat alarm oH is triggered.
0: Ramp to Stop using the active decel time.
1: Coast to Stop.
2: Fast-stop using the time set in C1-09.
3: Alarm Only. Drive continues running, but displays an
alarm.
Settings 0 through 2 trigger a fault relay if the heatsink
becomes too hot.
Selects the detection of input current phase loss, power
supply voltage imbalance, or main circuit electrolytic
capacitor deterioration.
0: Disabled
1: Enabled
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
positive torque
L7-01
motor
r/min
FWD
L7-03
negative torque
= 20) will
Control
Mode
Range
Def.
V/f OL V P M
0 to 300 150% A A A
0.0 to 10.0 0.1 s A A A
0 to 300 200% − A −
0 to 300 200% − A −
0 to 300 200% − A −
0 to 300 200% − A −
200
− A −
5 to 10000
ms
− A −
0, 1
0
0,1
0
A A A
50 to 130
A A A
<11>
0 to 3
3
A A A
0,1
1
A A A
Addr.
Pg.
Hex
4A5
199
4A6
199
4A7
199
4A8
199
4A9
199
4AA
199
4AC
199
4C9
200
4AD
200
4AE
200
4AF
201
4B1
201