B.3 Parameter Table

◆ C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions
and carrier frequency selections.
No.
Name
C1-01
Acceleration Time 1
<15>
C1-02
Deceleration Time 1
<15>
C1-03
Acceleration Time 2
<15>
C1-04
Deceleration Time 2
<15>
C1-05
Acceleration Time 3 (Motor
2 Accel Time 1)
<15>
C1-06
Deceleration Time 3 (Motor
2 Decel Time 1)
<15>
C1-07
Acceleration Time 4 (Motor
2 Accel Time 2)
<15>
C1-08
Deceleration Time 4 (Motor
2 Decel Time 2)
<15>
C1-09
Fast-Stop Time
Accel/Decel Time Setting
C1-10
Units
Accel/Decel Time
C1-11
Switching Frequency
C2-01
S-Curve Characteristic at
Accel Start
<15>
C2-02
S-Curve Characteristic at
Accel End
<15>
C2-03
S-Curve Characteristic at
Decel Start
<15>
C2-04
S-Curve Characteristic at
Decel End
<15>
326
Description
C1: Acceleration and Deceleration Times
Use C1 parameters to configure motor acceleration and deceleration.
Sets the time to accelerate from 0 to maximum
frequency.
Sets the time to decelerate from maximum frequency to
0.
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 2 are selected by a
digital input.
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 2 are selected by a digital
input.
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 3 are selected by a
digital input.
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 3 are selected by a digital
input.
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 4 are selected by a
digital input.
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 4 are selected by a digital
input.
Sets the time to decelerate from maximum frequency to
0 for the multi-function input fast-stop function.
Note: This parameter is also used by selecting "Fast-
Stop" as a Stop Method when a fault is detected.
Sets the resolution of C1-01 to C1-09.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
Sets the frequency for automatic acceleration/
deceleration switching.
Below set frequency: Accel/Decel Time 4
Above set frequency: Accel/Decel Time 1
The multi-function input "Accel/Decel Time 1" or
"Accel/Decel Time 2" take priority.
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
The S-curve can be controlled in the four points shown
below.
Run
ON
command
Output
frequency
C2-02
C2-01
S-curve is used to further soften the starting and
stopping ramp. The longer the S-curve time, the softer
the starting and stopping ramp.
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Range
0.0 to
6000.0
<5>
0.0 to
6000.0
<5>
0, 1
0.0 to 400.0
Hz
0.00 to
10.00
0.00 to 10.0 0.20 s A A A
OFF
0.00 to 10.0 0.20 s A A A
C2-03
C2-04
Time
0.00 to 10.0 0.00 s A A A
Control
Mode
Addr.
Def.
Hex
V/f OL V P M
S
S
S
200
S
S
S
201
A A A
202
A A A
203
10.0 s
A A A
204
A A A
205
A A A
206
A A A
207
10.0 s A A A
208
1
A A A
209
0.0 Hz A A A
20A
0.20 s
A A A
20B
<2>
20C
20D
20E
Pg.
133
133
133
133
133
133
133
133
134
134
135
135
135
135
135