B.3 Parameter Table
No.
Name
Digital Operator
o2-06
Disconnection Operation
o2-07
Motor Direction at Power
Up when Using Operator
<18>
o2-09
Reserved
Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.
o3-01
Copy Function Selection
o3-02
Copy Allowed Selection
Cumulative Operation Time
o4-01
Setting
Cumulative Operation Time
o4-02
Selection
Cooling Fan Operation
o4-03
Time Setting
Capacitor Maintenance
o4-05
Setting
DC Bus Pre-charge Relay
o4-07
Maintenance Setting
o4-09
IGBT Maintenance Setting
o4-11
U2, U3 Initialization
o4-12
kWh Monitor Initialization
Number of Run Commands
o4-13
Counter Initialization
<10> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<11> Default setting is determined by the drive model selection set in parameter o2-04.
<15> Parameter can be changed during run.
<18> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<41> This parameter is valid from software versions 6002 and later. Set in units of 10 hours. Setting o4-03 to 30 will have the start counting the
cooling fan operation time from 300 hours, and U4-03 will display 300H. Earlier software versions set the cooling fan operation time in 1 hour
units.
354
Description
Sets drive action when the digital operator is removed in
LOCAL mode or with b1-02 = 0.
0: The drive will continue operation
1: The drive will trigger a fault (oPR) and the motor will
coast to stop
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to
the digital operator.
o3: Copy Function
Selects the copy function operation.
0: No action
1: READ
2: COPY
3: VERIFY
NOTE: When using the copy function, the drive model
number (o2-04) and the software number (U1-14) must
match or an error will occur.
Locks the READ operation to prevent accidental
overwriting of the data stored in the LED operator.
0: READ operation prohibited
1: READ operation allowed
o4: Maintenance Monitor Settings
Use o4 parameters to perform maintenance.
Sets the value for the cumulative operation time of the
drive in units of 10 h.
Determines, how the cumulative operation time (U4-01) is
counted.
0: Logs power-on time
1: Logs operation time when the drive output is active
(output operation time).
Sets the value of the fan operation time monitor U4-03 in
units of 10 h.
<41>
Sets the value of the capacitor maintenance time monitor
U4-05.
Sets the value of the Soft Charge Bypass Relay
Maintenance monitor U4-06.
Sets the value of the IGBT Maintenance monitor U4-07.
Selects if U2-
(Fault Trace), U3-
monitors are reset at drive initialization.
0: Save the contents of the U2-
parameters.
1: Reset the contents of the U2-
parameters.
Selects if U4-10 and U4-11 (kWh monitor) are reset at
drive initialization.
0: Save the contents of U4-10 and U4-11.
1: Reset the contents of U4-10 and U4-11.
Selects if the Run command counter (U4-02) is reset at
drive initialization.
0: Save the motor speed monitor (U4-02).
1: Reset the motor speed monitor (U4-02).
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Range
0, 1
0 to 1
0 to 3
0, 1
0 to 9999
0 to 1
0 to 9999
0 to 150
0 to 150
0 to 150
(Fault History)
and U3-
0 to 1
and U3-
0 to 1
0 to 1
Control
Mode
Addr.
Def.
Pg.
Hex
V/f OL V P M
0
A A A
50A
216
0
A A A
527
216
50D
216
0
A A A
515
216
0
A A A
516
0
A A A
50B
217
0
A A A
50C
217
0
A A A
50E
217
0%
A A A
51D
217
0%
A A A
523
217
0%
A A A
525
218
0
A A A
510
218
0
A A A
512
218
0
A A A
528
218