Page 1
タイトル 超える場 ションの場合①と②の順番が逆になります。 以降を成 YASKAWA AC Drive T1000A AC Drive for Textile Applications ここまで Technical Manual Type: CIMR-TA Models: 200 V Class: 0.55 to 110 kW 400 V Class: 0.55 to 185 kW To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
Page 2
Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Refer to Drive Alarms, Faults, and Errors on page 272 Refer to Troubleshooting without Fault Display on page 305. Standards Compliance Refer to European Standards on page 476 Refer to UL Standards on page 481. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 4
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 12
E.3 User Setting Table ..........494 Index ..........................500 Revision History ......................514 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Preface & General Safety This section provides safety messages pertinent to this product that, if not heeded, may result in fatality, personal injury, or equipment damage. Yaskawa is not responsible for the consequences of ignoring these instructions. I.1 PREFACE ............14 I.2 GENERAL SAFETY .
Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/ or the manual. • When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
Do not attempt to modify or alter the drive in any way not explained in this manual. Failure to comply could result in death or serious injury. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Do not allow unqualified personnel to use equipment.
Page 17
Failure to comply may cause damage to the electrical components in the drive. Do not pack the drive in wooden materials that have been fumigated or sterilized. Do not sterilize the entire package after the product is packed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Fast Stop function is able to. Options The B1, B2, +1, +2, and +3 terminals are used to connect optional devices. Connect only T1000A-compatible devices. Installation...
Page 19
Selecting a Circuit Breaker or Leakage Circuit Breaker Yaskawa recommends installing equipment for residual current monitoring/detection (RCM/RCD) to the power supply side. The RCM/RCD should be designed for use with an AC drive (e.g. Type B according to IEC 60755).
Vibration and Shock T1000A lets the user choose between high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce motor oscillation. Take particular caution when using a variable speed drive for an application that is conventionally run from line power at a constant speed.
A split-phase start or a repulsion start can end up burning out the starter coils because the internal centrifugal switch is not activated. T1000A is for use with 3-phase motors only.
Warranty Information Restrictions T1000A was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health. Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<3> These values assume the carrier frequency is set to 2 kHz. Note: Current derating is required when setting the carrier frequency higher. Refer to Carrier Frequency Derating on page 359 details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
1.2 General Description u Control Mode Selection Table 1.2 gives an overview of the T1000A control modes and their various features. Table 1.2 Control Modes and their Features Induction Motors, Motor Type Induction Synchronous Induction Motors Permanent Magnet Motors Comments...
Page 28
<4> These units fulfill IP20 requirements, but the wire bending space provided is lower than recommended in the IEC61800-5. <5> Drives with these specifications do not guarantee complete protection for the specified environmental condition. <6> Contact Yaskawa for information about using drives in environments other than specified in this manual. Note: 1. Refer to Drive Models on page 29 for differences regarding enclosure protection types and component descriptions.
I - Front cover screw J - Digital operator K - Drive Cover L - Terminal cover M - Bottom front cover N - Bottom cover O - Rubber bussing YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Circuit Wiring on page Analog/PTC Input Selection on page G – Main circuit terminal (Refer to Wiring the Main Circuit Terminal on page 59 Figure 1.2 Front View of Drives YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 32
1.5 Component Names YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Do not carry the drive by the front cover or the terminal cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 35
This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is not explosion-proof, always install it in a safe place. Never lift the drive up while the cover is removed. This can damage the terminal board and other components. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Installation Orientation and Spacing Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling. Figure 2.1 Not good Not good Figure 2.1 Correct Installation Orientation YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 37
Note: When installing drives of different heights in the same enclosure panel, the tops of the drives should line up. Leave space between the top and bottom of stacked drives for easy cooling fan replacement if required. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The digital operator is flush Installation Support Set B with the outside of the panel. Phillips screwdriver (#1) (for use with threaded studs that are EZZ020642B Wrench (7 mm) fixed to the panel) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 39
Digital Operator Phillips recessed pan head machine screw × 2 Enclosure panel Unit: mm Figure 2.6 External/Face-Mount Installation Figure 2.7 Unit: mm Figure 2.7 Panel Cut-Out Dimensions (External/Face-Mount Installation) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 40
2.2 Mechanical Installation Internal/Flush-Mount An internal flush-mount requires an installation support set that must be purchased separately. Contact your Yaskawa representative to order an installation support set and mounting hardware. Figure 2.8 illustrates how to attach the Installation Support Set A.
When installing a dynamic braking resistor or optional Braking Resistor Unit, perform all wiring exactly as specified in the wiring diagrams provided. Failure to do so can result in fire. Improper wiring may damage braking components. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 45
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.
EDM (Safety Electronic Device Monitor) jumper shielded line Safety relay / <12> controller twisted-pair shielded line − − control circuit terminal main circuit terminal Figure 3.1 Drive Standard Connection Diagram (example: CIMR-T 2A0040) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 47
2-Wire sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of the drive and may cause injury. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Connect ground wiring first, followed by the main circuit, and then wire the control circuit. Power lines and signal wiring exit through the opening provided. Figure 3.5 Reattaching the Terminal Cover YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Connect ground wiring first, followed by the main circuit, and then wire the control circuit. Power lines and signal wiring exit through the opening provided. Figure 3.8 Reattaching the Terminal Cover YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Remove the terminal cover and the digital operator. Loosen the installation screw on the front cover. Use a straight-edge screwdriver to loosen the hooks on each side of the cover that hold it in place. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 53
Figure 3.14 Reattach the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A0362) Once the hooks have connected to the drive, press firmly on the cover to make sure it locks into place. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(models CIMR-T 2A0004 to 2A0138 and 4A0002 to 4A0072), connect the braking resistor to the B1 terminal and the negative terminal. • Refer to UL Standards Compliance on page 481 for information on UL compliance. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 55
U/T1, V/T2, W/T3 35 to 70 18 to 23 (159 to 204) –, +1 – 50 to 70 2A0138 B1, B2 – 25 to 70 9 to 11 (79.7 to 97.4) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 56
Note: Refer to the related instruction manuals for the applicable wire gauges when connecting peripheral devices to terminals -, +1, +3, B1, and B2. Contact your Yaskawa representative or the nearest Yaskawa sales office directly for consultation if using a wire gauge not listed in the manual.
Page 57
R/L1, S/L2, T/L3 50 to 95 U/T1, V/T2, W/T3 70 to 95 18 to 23 –,+1 – 35 to 95 4A0165 (159 to 204) – 50 to 95 25 to 35 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: Refer to the related instruction manuals for the applicable wire gauges when connecting peripheral devices to terminals -, +1, +3, B1, and B2. Contact your Yaskawa representative or the nearest Yaskawa sales office directly for consultation if using a wire gauge not listed in the manual.
Page 59
Improper wiring connections could cause the braking resistor to overheat and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Use DIP switch S4 on the terminal board to selection between analog or PTC input. Frequency reference common Ground for shielded lines and option cards – – E (G) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC Figure 3.17 Control Circuit Terminal Arrangement YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Wire Size on page NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical interference. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 63
NOTICE: The signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC DIP Switch S2 RS-422/485 Termination Resistor Figure 3.22 Locations of Jumpers and Switches on the Terminal Board YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency reference. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Table 3.18 MEMOBUS/Modbus Switch Settings S2 Position Description Internal termination resistor ON Internal termination resistor OFF (default setting) Note: Refer to MEMOBUS/Modbus Communications on page 445 for details on MEMOBUS/Modbus. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The drive can connect to the USB port of a PC using a USB 2.0, AB type cable (sold separately). DriveWizard Plus can then be used to monitor drive performance and manage parameter settings. Contact Yaskawa for more information on DriveWizard Plus.
Properly separate control circuit wiring and main circuit wiring. – Analog signal line wiring should not exceed 50 m. – Safe Disable input wiring should not exceed 30 m. – YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The holding brake should be wired so that it is activated by an external sequence when a fault occurs, the power is shut off, or an emergency switch is triggered. Failure to comply could result in death or serious injury. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. To disable the LO/RE key to prohibit switching between LOCAL and REMOTE, set parameter o2-01 to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When a display other than the output frequency When the display shows the output frequency — monitor is shown. DIGITAL OPERATOR JVOP-182 DIGITAL OPERATOR JVOP-182 DIGITAL OPERATOR JVOP-182 As illustrated in this FOUT FOUT FOUT manual YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure 4.2 RUN LED Status and Meaning Figure 4.3 Drive output frequency during stop STOP STOP 6 Hz 0 Hz Frequency setting RUN LED Flashing Figure 4.3 RUN LED and Drive Operation YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<1> Reverse can only be selected when the drive is set for LOCAL. Details on switching between forward and reverse can be found in Navigating the Drive and Programming Modes on page Figure 4.4 Digital Operator Menu and Screen Structure YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(o1-01 = 106). Refer to o1: Digital Operator Display Selection on page 407. (default) DIGITAL OPERATOR JVOP-182 FOUT Monitor Display Lists the monitor parameters (U - parameters) available in the drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 78
This feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency reference as soon as changes are made without requiring the ENTER key, set o2-05 to 1. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: The Verify Menu will not display parameters from the A1 group (except for A1-02) even if those parameters have been changed from their default settings. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings. <2> To return to the previous menu without saving changes, press the ESC key. Figure 4.6 Setup Group Example YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When setting the multi-function input terminals, setting H1- to 1 disables the LO/RE key on the digital operator. Refer to H1 Multi-Function Digital Input Selections on page 388 for a list of digital input selections. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
2. Auto-Tuning should be performed again after installing an AC reactor or other such components to the output side of the drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Couple the load or machine to the motor. Run the machine and check for desired operation. Return to Flowchart Figure 4.8 Simple Motor Setup with Energy Savings or Speed Search YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<4> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB function. Figure 4.9 Flowchart A2: High Performance Operation Using OLV or CLV YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Return to Flowchart <1> Enter the motor code to E5-01 when using a Yaskawa PM motor (SMRA Series, SSR1 Series, and SST4 Series). If using a motor from another manufacturer, enter FFFF. <2> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 277 Fault for more information and possible solution. are lit. External fault (example) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
PG Number of pulses per revolution T1-08 <1> <1> <1> Motor no-load current T1-09 Motor rated Slip T1-10 Motor iron loss T1-11 <1> Input data is needed for CLV/PM only. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 88
Inertia Tuning and ASR Gain Auto-Tuning. Refer to Auto-Tuning for Permanent Magnet Motors on page 88 for details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Stationary Auto-Tuning 1 and 2 • Perform these tuning methods when using a vector control mode but Rotational Auto-Tuning cannot be performed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The display automatically returns to the display shown in Step 3. <1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1- = 16). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 91
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being performed. Auto-Tuning finishes in approximately one to two minutes. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
If no data is available, enter approximately 90% of the rated voltage printed on the motor nameplate. Note that this might increase the output current reducing the overload margin. Name Setting Range Default T1-03 Motor Rated Voltage 0.0 to 255.5 V 200.0 V <1> YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 93
(0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
T2-02: PM Motor Code Selection If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code for the motor in parameter T2-02. This will automatically set parameters T2-03 through T2-14. If using a specialized motor or one designed by a manufacturer other than Yaskawa, set T2-02 to FFFF.
Page 95
T2-12: PM Motor q-Axis Inductance Enter the q axis inductance per motor phase. Name Setting Range Default T2-12 PM Motor q-Axis Inductance 0.00 to 600.00 mH Depending on T2-02 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 96
Z pulse is unknown or if the PG encoder is replaced, perform Z pulse tuning. Name Setting Range Default T2-17 Encoder Z-Pulse Offset (Δθ) -180.0 to 180.0 deg 0.0 deg YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
T3-03: Motor Inertia Enter the inertia of the motor. This value is used to determine the load inertia using the test signal response. The default setting is for a Yaskawa standard motor as listed in the motor inertia table. Name...
DIGITAL OPERATOR JVOP-182 FOUT STOP RESET ENTER The drive should operate normally. Press to stop the motor. RUN flashes until the motor comes to a STOP complete stop. Flashing YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• If the application permits running the load in the reverse direction, try changing motor direction and the frequency reference while watching for abnormal motor oscillation or vibration. • Correct any problems that occur with hunting, oscillation, or other control-related issues. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
A1-05: A1-01, A1-02, A1-03, and A2-01 through A2-33. Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously press the key and key. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
DriveWizard is a PC software tool for parameter management, monitoring, and diagnosis. DriveWizard can load, store, and copy drive parameter settings. For details, refer to Help in the DriveWizard software. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(set “2” for 4 to 20 mA, or “3” for 0 to 20 mA). Set the proper current to terminal A2. (-10 to +10 V, 4 to 20 mA or 0 to 20 mA). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 103
Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2, H3-08 for analog input A3) until the frequency reference value reaches the desired minimum value. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 104
4.10 Test Run Checklist YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: When changing control modes, all parameter settings depending upon the setting of A1-02 will be reset to the default. Parameter Name Setting Range Default A1-02 Control Method Selection 0, 1, 2, 3, 5, 6, 7 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 107
If parameters on a certain drive have been edited and then a different terminal block is installed with different settings saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the terminal block memory, set A1-02 to 5550. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 108
Note: Because A1-05 is hidden, it will not be displayed by simply pressing the key. “05” flashes Press the key. to enter the password. Press to save what was entered. The display automatically returns to the display shown in step 5. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
If A1-01 is then set to 1, the access level can be restricted so that users can only set and refer to the specific parameters saved as User Parameters. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 110
16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. User Parameters can be accessed using the Setup Mode of the digital operator. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
H3-10 = 0 Make sure to set DIP switch S1 on the H3-11 H3-12 (Frequency Bias) terminal board to “I” for current input. 0 to 20 mA H3-09 = 3 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 112
Setting 40, 41: Forward run, Reverse run command for 2-wire sequence on page 187. • 2-wire sequence 2: Two inputs (Start/Stop-FWD/REV). Also refer to Setting 42, 43: Run and direction command for 2-wire sequence 2 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 113
DC Injection at start (Refer to b2-03: DC Injection Braking Time at Start on page 119) or Speed Search (Refer to b3: Speed Search on page 121). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 114
Figure 5.6 Run command Output Drive output shut off frequency Run wait time t Figure 5.6 Coast to Stop with Timer YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 115
PM: Zero Spd. Contr. E1-09 b2-01 Zero Speed Level Motor b2-03 b2-04 Speed Zero Speed Time at Stop Zero Speed Time at Start Figure 5.8 Run at the Frequency Reference YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 116
The state of a digital input is read once. If the state has changed, the input command is immediately processed. With this setting the drive responds more quickly to digital inputs, but a noisy signal could cause erroneous operation. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 117
Switching motor phases will reverse the direction of the motor. Parameter Name Setting Range Default b1-14 Phase Order Selection 0 or 1 Setting 0: Standard phase order Setting 1: Switched phase order YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at stop. Once the output frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 119
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), DC Injection or Speed Search should be used to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 120
0.00 s Note: Short Circuit Braking cannot prevent a PM motor from being rotated by an external force. To prevent the load from rotating the motor, use DC Injection. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure 5.16 Current Detection Speed Search after Power Loss Note: After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 122
Once AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored before starting Speed Search. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 123
Closed: Activate Current Detection Speed Search from the External Search Command 2 frequency reference. To activate Speed Search by a digital input, the input must always be set together with the Run command, or the Run YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 124
Search can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close completely. Name Setting Range Default b3-05 Speed Search Delay Time 0.0 to 100.0 s 0.2 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 125
SEr fault will occur and the drive will stop. Name Setting Range Default b3-19 Number of Speed Search Restarts 0 to 10 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Name Setting Range Default b4-01 0.0 to 3000.0 s 0.0 s Timer Function On-Delay Time b4-02 0.0 to 3000.0 s 0.0 s Timer Function Off-Delay Time YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
To better demonstrate how PID works, the diagram below shows how the PID output changes when the PID input (deviation) jumps from 0 to a constant level. Figure 5.21 PID input Time PID output I control D control PID Output P control Time Figure 5.21 PID Operation YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 128
Analog Input A2 Set H3-10 = 16 Analog Input A3 Set H3-06 = 16 Note: A duplicate allocation of the PID differential feedback input will result in an oPE alarm. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 130
D control is disabled by setting b5-05 to zero seconds. Name Setting Range Default b5-05 Derivative Time (D) 0.00 to 10.00 s 0.00 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 131
Negative PID output will be limited to 0 and the drive output will be stopped. Setting 1: Reverse Enabled Negative PID output will cause the drive to run in the opposite direction. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 132
If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH - Feedback High” fault will be displayed. Both events trigger a fault output (H1- = E) and cause the drive to stop the motor. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 133
• The PID Sleep function is always active, even if PID control is disabled. • The PID Sleep function stops the motor according to the stopping method in b1-03. The parameters necessary that control the PID Sleep function are explained below. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 134
Parameter b5-19 is used as PID setpoint. b5-19: PID Setpoint Value Used as the PID setpoint if parameter b5-18 = 1. Name Setting Range Default b5-19 PID Setpoint Value 0.00 to 100.00% 0.00% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 135
Setting 0: Frequency Reference after PID Monitor U1-01 displays the frequency reference increased or reduced for the PID output. Setting 1: Frequency Reference Monitor U1-01 displays the frequency reference value. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Negative PID output will cause the drive to run in the opposite direction. u b6: Dwell Function The Dwell function is used to temporarily hold the frequency reference at a predefined value for a set time, then continue accelerating or decelerating. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Sets the gain level for Energy Saving. A higher value results in lower magnetization of the motor and thereby less energy consumption. However, if b8-02 is too low, the motor may stall. Name Setting Range Default b8-02 Energy Saving Gain 0.0 to 10.0 Determined by A1-02 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 138
When E5-01 (Motor Code Selection) is set to 1 or 2 , the automatically calculated value will be set. When the value is set automatically, it cannot be changed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
= 33) will be triggered when the motor reaches the position Zero Servo position plus or minus b9-02. Name Setting Range Default b9-02 Zero Servo Completion Width 0 to 16383 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Accel/Decel Time Selection 1 (Terminals S1 to S8, H1- = “7”) Accel/Decel Time Selection 2 (Terminals S1 to S8, H1- = “1A”) Figure 5.27 Timing Diagram of Accel/Decel Time Change YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 141
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
C3-01: Slip Compensation Gain This parameter sets the gain for the motor slip compensation function. Although this parameter rarely needs to be changed, adjustments might be needed under the following circumstances: YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 143
Slip compensation is enabled during regenerative operation, and at frequencies as low as 2 Hz. The drive uses the motor rated slip set in E2-02 to automatically calculate the frequency range where compensation will be disabled. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 144
(frequency reference > E3-06), it is increased based on C3-23 and the output frequency as shown in Figure 5.31. Figure 5.31 E3-04 E3-06 × C3-23 C3-23 Output Frequency E3-06 E3-04 Base Maximum Frequency Frequency Figure 5.31 Slip Compensation Limit YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Although C4-02 rarely needs to be changed, adjustments may help in the following situations: • If the motor vibrates, increase C4-02. • If the motor responds too slowly to changes in the load, decrease C4-02. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure 5.32 Output frequency Frequency reference ASR limit Change Detected speed rate limiter C5-01 C5-05 C5-03 C5-02, C5-04 Figure 5.32 Speed Control Block Diagram for V/f Control with PG YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 147
ASR. Though the parameters listed below are for motor 1, the same changes can be made to the corresponding motor 2 parameters when running a second motor. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 148
P and I setting I = C5-02 P = C5-03 I = C5-04 Motor speed E1-09 E1-04 Min. output frequency Max. output frequency Figure 5.34 ASR Gain and Integral Time in V/fw/PG YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 149
Increase this setting gradually in increments of 0.01 for loads with low rigidity, or when oscillation is a problem. Note: This parameter rarely requires adjustment. Parameter Name Setting Range Default C5-06 ASR Primary Delay Time Constant 0.000 to 0.500 s Determined by A1-02 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 150
These parameters function for motor 2 in the same way that C5-01 through C5-04 function for motor 1. For more details, C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 148. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 151
Integral operation is always enabled. C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio These parameters function for motor 2 in the same way that C5-17 and C5-18 function for motor 1. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Carrier Frequency 2.0 kHz 12.5 kHz (10.0 kHz) 5.0 kHz (4.0 kHz) 15.0 kHz (12.0 kHz) 8.0 kHz (6.0 kHz) User defined (C6-03 to C6-05) 10.0 kHz (8.0 kHz) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 153
Setting Range Default 2 when C6-02 = 1 C6-06 PWM Method 0 to 2 0 for all other C6-02 settings 0: 2-phase/3-phase conversion 1: 2-phase modulation 2: 3-phase modulation YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 154
In such cases, first set C6-03 to high value, then set C6-09 = 1. Parameter Name Setting Range Default C6-09 Carrier Frequency during Rotational Auto-Tuning 0, 1 Setting 0: 5 kHz Setting 1: Same value set to C6-03 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When setting terminal A1's analog input to Multi-Step Speed 1, set b1-01 to 1, and when setting d1-01 (Frequency Reference 1) to Multi-Step Speed 1, set b1-01 to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Sets the upper limit for the frequency reference value that is input from frequency reference source 2 (b1-15). The limit applies to any source selected in parameter b1-15. The value is set as a percentage of the maximum output frequency. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
S- reference source frequency reference source in parameter b1-01 or b1- curves are applied to the speed limit value. Speed Limit <1> Parameter d5-04 d5-03 = 2 – YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 160
Setting Range Default d5-01 Torque Control Selection 0 or 1 Setting 0: Disabled Speed Control will be active. Also use this setting when H1- = 71 (Speed/Torque Control Switch). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 161
The speed limit bias is applied in both directions, the speed limit and the opposite direction. Setting 1: Enabled The speed limit bias is applied in the opposite direction of the speed limit only. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Sets the maximum level to what the Field Forcing function can boost the excitation current reference. The value is set as a percentage of the motor no load current. Parameter Name Setting Range Default d6-06 Field Forcing Limit 100 to 400% 400% Note: Adjustment is not normally required. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
E1-12 Middle Output Frequency Voltage 2 0.0 to 255.0 V 0.0 V <4> <4> <5> <6> E1-13 Base Voltage 0.0 to 255.0 V 0.0 V <4> <4> <5> <7> YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and the formula below: E2-02 = f - (n × p)/120 (f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 166
E2-08. This coefficient is used when operating with constant output. Parameter Name Setting Range Default E2-08 Motor Iron-Core Saturation Coefficient 2 E2-07 to 0.75 0.75 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 167
Enter the no-load current at rated frequency and rated voltage to E2-03. The no-load current is not usually listed on the nameplate. Contact the motor manufacturer if the data cannot be found. The default setting of the no-load current is for performance with a 4-pole Yaskawa motor. Setting the Number of Motor Poles Only required in V/f Control with PG and Closed Loop Vector Control.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01). <3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). <4> Parameter ignored when E3-11 and E3-12 are set to 0.0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer Table A.2 Table A.3.) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 170
Note: The maximum applicable motor capacity varies based on whether the drive is set for Normal Duty or Heavy Duty performance (C6-01). For more information, refer to Model Number and Nameplate Check on page YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
A1-03. E5-01: Motor Code Selection When Yaskawa motors are used, set the motor code for the PM motor being used. Depending on the motor code entered, the drive automatically sets several parameters to appropriate values.
Page 172
Note: Ensure that E5-09 = 0 when setting parameter E5-24. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or if neither parameter is set to 0. When E5-01 = FFFF, then E5-09 = 0.0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
F1: PG Speed Control Card Settings Yaskawa offers two motor encoder PG option cards: PG-B3 and PG-X3. When using only one PG option card, use the CN5-C port. For two PG option cards, use ports CN5-C and CN5-B. When one of the multi-function input terminals has...
Page 174
0 to 1000 F1-34 CN5-B 0 to 1000 PG 2 Gear Teeth 2 Note: A gear ratio of 1 will be used if any of these parameters is set to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 175
Note: It is not possible to switch between motors when using a PM motor. Parameter Name Setting Range Default F1-30 PG Option Card Port for Motor 2 Selection 0, 1 Setting 0: CN5-C Setting 1: CN5-B YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
F3-03 = 0: 100%/255 (-255 to +255) F3-03 = 1: 100%/4095 (-4095 to +4095) F3-03 = 2: 100%/30000 (-33000 to +33000) Note: BCD input when o1-03 = 2 or 3. Units are determined by o1-03. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Use the digital operator to display the monitor bias for terminal V2 (F4-06). Make sure that the voltage output is 0% of the monitor level selection for terminal V2 (F4-03). Adjust the setting to parameter F4-06 accordingly while watching the read out of the meter connected to terminal YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Some parameters apply to all communication option cards, while some parameters are used only for certain network options. F6-01: Communications Error Operation Selection Determines drive operation if a communication error occurs. Parameter Name Setting Range Default F6-01 Communications Error Operation Selection 0 to 3 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 179
Setting 0: Do not reset parameters F6- when the drive is initialized with A1-03 Setting 1: Reset F6- when the drive is initialized with A1-03 Note: F6-08 is not reset when the drive is initialized. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
MECHATROLINK Parameters Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK network. For details on parameter settings, refer to the YASKAWA AC Drive-Option Card MECHATROLINK-II Installation Manual and Technical Manual. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Accel/decel time selection 2 Short Circuit Braking (N.O.) Program lockout Short Circuit Braking (N.C.) 20 to 2F External fault Forward/reverse detection (V/f control with simple PG) PID integral reset YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 182
3. The default setting of the drive is not to allow switching between LOCAL and REMOTE during run. To allow the drive to switch between LOCAL and REMOTE during run, Refer to b1-07: LOCAL/REMOTE Run Selection on page 117. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 183
Acceleration or deceleration will resume once the input is opened again. Setting B: Drive overheat alarm (oH2) Triggers an oH2 alarm when the contact closes. Because this is an alarm, drive operation is not affected. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 184
Up or Down command is set. Figure 5.49 shows an Up/Down function example with a lower frequency reference limit set by d2-02, and the frequency reference hold function both enabled and disabled. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 185
• To trigger the Fast Stop function with a N.O. switch, set H1- = 15. • To trigger the Fast Stop function with a N.C. switch, set H1- = 17. Figure 5.51 shows an operation example of Fast Stop. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 186
Used to select accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command. Refer to C1-01 to C1-08: Accel, Decel Times 1 to 4 on page 140 for details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 187
When an input terminal set to 40 closes, the drive operates in the forward direction. When an input set for 41 closes, the drive will operate in reverse. Closing both inputs at the same time will result in an external fault. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 188
This function can be used to warm up the motor before starting it, and to keep the motor warm when stopped. The DC Injection 2 command can be activated using a digital input (H1- = 60). A Run command is not necessary to use this function. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 189
(i.e., a new Run command is required). If the input is opened while the drive is running, the drive will stop according to the stop method set to b1-03 (Refer to b1-03: Stopping Method Selection on page 113). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
During speed limit in Torque Control Frequency reference source Zero Servo complete Run command source During frequency output Torque detection 1 (N.O.) Drive enabled Frequency reference loss Watt hour pulse output YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 191
Output frequency or motor speed does not match the frequency reference while the drive is running. Closed Output frequency or motor speed is within the range of frequency reference ±L4-02. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 192
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02. Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 193
Setting 8: During baseblock (N.O.) Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no main circuit voltage is output. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 194
Setting 12: Timer output This setting configures a digital output terminal as output for the timer function. Refer to b4: Delay Timers on page 126 for details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 195
Figure 5.61 User Set Speed Agree 2 Example with a Positive L3-04 Value Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 223 for more details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 196
Detection 4 Figure 5.63 Frequency Detection 4 Example with Positive L3-04 Value Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 223 for more details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 197
Components performance life is displayed as a percentage on the digital operator screen. Refer to Periodic Maintenance on page 317. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 198
LOCAL: The digital operator is used as frequency reference and Run command source Setting 3D: During Speed Search Output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 121 for details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 199
Examples: • For inverse output of “8: During baseblock”, set 108. • For inverse output of “4A: During KEB” set 14A. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 200
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off. Figure 5.66 H2-06 (Pulse Output Unit) Integral Power (every 100 ms) H2-01 to 03 Multi-function Output) 0.2 s Figure 5.66 Watt Hour Output Example YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input. When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 202
Setting 2: 4 to 20 mA Current Input The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 203
These parameters rarely need adjustment. Name Setting Range Default H3-16 Terminal A1 Offset –500 to 500 H3-17 Terminal A2 Offset –500 to 500 H3-18 Terminal A3 Offset –500 to 500 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 204
Acceleration/deceleration gain from 1 to 10 V (10 V) × 10 (%) = Input Voltage (V) 10 V 1V 2V Figure 5.69 Accel/Decel Time Gain with Analog Input Terminal YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 205
Terminal A3 Analog/PTC Input Selection on page 67 for details on setting S4. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) on page 215 for further explanation. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 206
When S3-04 = 0.5, changing the output voltage gain from 100% to 200% takes 0.5 s for the actual output voltage gain to reach 200%. Figure 5.73 Output Voltage Gain 200% 100% S3-04 0.5 s Figure 5.73 Example of How to Set the Output Voltage Gain YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Adjust the setting to parameter H4-06 accordingly while watching the read out of the meter connected to terminal Example 1: To have an output signal of 5 V at terminal FM when the monitored value is at 100%, set H4-02 to 50%. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
A one track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 209
H6-02 (pulse input scaling). Make sure the pulse input bias (H6-04) is 0% and the gain (H6-03) is 100%. Decide the signal used for detecting the direction. If a digital input is used, set H1- = 7E. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 210
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency becomes the detection time for PG disconnect (F1-14). Name Setting Range Default H6-08 Pulse Train Input Minimum Frequency 0.1 to 1000.0 Hz 0.5 Hz YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
100% load can trigger motor rated base frequency (check the motor nameplate or overload protection (oL1). A fault is output and the specifications). motor will coast to stop. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 212
(oL1). Continuous speed. Built with effective cooling capabilities. The drive fault output closes and the motor coasts to stop. Motor Speed (%) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 213
(check the motor nameplate or overload protection (oL1). A fault is output and the specifications). motor will coast to stop. Continuous 05 33 100 120 167 200 Speed (%) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 214
• Hot start: Motor protection operation time in response to an overload situation that occurred during sustained operation at rated current. Figure 5.78 Operation time (minutes) Cold start Hot start Motor current (%) E2-01 = 100% motor current Figure 5.78 Motor Protection Operation Time YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 215
PTCs to be connected in series. Figure 5.80 Tr’ Figure 5.80 Motor PTC Characteristics Overheat detection using a PTC can be set up by parameters L1-03, L1-04, and L1-05 as explained below. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 216
Determines whether or not to hold the current value of the electrothermal motor protection (L1-01) when the power supply is interrupted. Name Setting Range Default L1-13 Continuous Electrothermal Operation Selection 0 or 1 Setting 0: Disabled Setting 1: Enabled YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
L2-05 Undervoltage Detection Level 150 to 250 Vdc 190 V <1> <2> <1> Values are for 200 V class drives and must be doubled for 400 V class drives. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Time at Stall Prevention during Acceleration on page 219). Once the output current falls 5% below the level set in L3-02, the drive stop decelerating and starts to accelerate again. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 219
The function is effective only in Open Loop Vector Control for PM motors and if parameter L3-01 is set to 1. Name Setting Range Default L3-22 Deceleration Time at Stall Prevention During Acceleration 0.0 to 6000.0 s 0.0 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 220
S6: Power KEB Function on page 260. Note: As the deceleration time is not constant, Intelligent Stall Prevention should not be used in applications where stopping accuracy is a concern. Use braking options instead. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 221
The level set in L3-06 is used throughout the entire speed range. Setting 1: Enabled The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 222
Sets a delay time from when the Stall Prevention level is reached and the actual Stall Prevention function is activated. Name Setting Range Default L3-27 Stall Prevention Detection Time 0 to 5000 ms 50 ms YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Setting Range Default L4-05 Frequency Reference Loss Detection Selection 0 or 1 Setting 0: Stop Drive follows the frequency reference (which is no longer present) and simply stops the motor. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 224
Drive Status (U1-12) 004BH bit4 During Speed Agree • Monitor Parameter Name Description U1-12 Drive Status The 5th digit from the right indicates whether speed agree has been reached or not. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1. Name Setting Range Default L5-04 Fault Reset Interval Time 0.5 to 600.0 s 10.0 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
An analog input signal can be used to set the detection level of torque detection 1 (L6-01). Refer to Multi-Function Analog Input Terminal Settings on page 204 for details on assigning a function to an analog input. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 227
These parameters determine the time required to trigger an alarm or fault after exceeding the levels in L6-02 and L6-05. Name Setting Range Default L6-03 0.0 to 10.0 s 0.1 s Torque Detection Time 1 L6-06 0.0 to 10.0 s 0.1 s Torque Detection Time 2 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Torque Limit Integral Time Constant 5 to 10000 ms 200 ms L7-07: Torque Limit Control Method Selection during Accel/Decel Selects the function of torque limit during acceleration and deceleration. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Internal Dynamic Braking Resistor Protection Selection (ERF type) 0 or 1 Setting 0: Disabled Disables braking resistor protection. Use this setting for any braking option other than the Yaskawa ERF type resistor. Setting 1: Enabled Enables protection for ERF type resistors.
Page 230
An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to stop. L8-09: Output Ground Fault Detection Selection Enables or disables the output ground fault detection. Name Setting Range Default L8-09 Output Ground Fault Detection Selection 0 or 1 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 231
Note: This setting should not be changed unless absolutely necessary. For proper drive protection and operation leave the Software CLA function enabled. Name Setting Range Default L8-18 Software Current Limit Selection 0 or 1 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 232
2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or when mounting a standard drive with the heatsink outside the cabinet. Name Setting Range Default L8-35 Installation Method Selection 0 to 3 Determined by o2-04 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 233
For an IP20 enclosure drive installed with at a minimum of 30 mm space to the next drive or a cabinet wall. Setting 1: Side-by-Side mounting For drives mounted according to Yaskawa’s Side-by-Side specifications (requires 2 mm between drives). Setting 2: NEMA Type 1 For drives compliant with NEMA Type 1 enclosure specifications.
Page 234
Sets the average number of times pull-out can occur at low speed. Name Setting Range Default L8-95 Average Pull-Out Frequency at Low Speed 1 to 50 Times 10 Times YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: Before making changes to the AFR parameters, make sure all motor parameters are set properly or perform Auto-Tuning. n2-01: Speed Feedback Detection Control (AFR) Gain Sets the internal speed feedback detection control gain in the AFR. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(ov), try increasing the deceleration time. • When a Run command is entered during Overexcitation Deceleration, overexcitation operation is cancelled and the drive will reaccelerate to the specified speed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
5.90. Feed Forward can only be used in Closed Loop Vector Control for induction or PM motors (A1-02 = 4 or 7), or in Advanced Open Loop Vector Control for PM motors (A1-02 = 6). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 238
Hz. n5-02 = rated rated • p is the number of motor poles (not pole pairs!). • T is the rated torque of the motor in N⋅m. rated YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
If the motor nameplate lists an Si value, enter that value here. Note: Parameter n8-01 is available only when in AOLV/PM or CLV/PM control mode. Name Setting Range Default n8-01 Initial Rotor Position Estimation Current 0 to 100% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 240
• If there is too much current when driving a light load at a constant speed, then slightly increasing this value. Note: This parameter is available only when using OLV/PM control mode. Name Setting Range Default n8-48 Pull-In Current 20 to 200% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 241
The inertia ratio between the motor and the load is between 1:30 and 1:50. Set n8-55 to 2 if an STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 1. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 242
There is normally no need to change this parameter from the default value. Note: This parameter is available in AOLV/PM only. Name Setting Range Default n8-69 Speed Calculation Gain 0.00 to 20.00 1.00 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When operating a high-speed motor at low speeds, n9-62 sets the frequency at which the drive stops compensating the switching delay in the DC bus. Name Setting Range Default n9-63 On-Delay Compensation Disable Frequency 0.0 to [E1-04] Hz 120.0 Hz YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
U1-16: output frequency after softstarter (accel/decel ramp generator) d1-01 to d1-17: frequency references 2. Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Run not possible If a Run command is entered, the drive will start running as soon as the LO/RE key is pushed to change from LOCAL to Run not possible REMOTE. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 246
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator. The ENTER key does not need to be pressed. The frequency reference is saved for 5 s after it is changed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Copy Allowed Selection Restricts or allows the use of the Copy function. Name Setting Range Default o3-02 Copy Allowed Selection 0 or 1 Setting 0: Disabled Setting 1: Enabled YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: The actual maintenance time will depend on the environment where the drive is used. Name Setting Range Default o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 249
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed, the counter value is erased and the display returns to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Conditions that Stop the Disturb Function Any one of the conditions below will stop the Disturb function. • The multi-function input terminal set to activate the Disturb command (H1- = 50) closes. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Determines the time the drive uses to change the frequency reference gain from 0.0% to the value assigned to S2-01. Name Setting Range Default S2-02 Frequency Reference Gain Change Ramp 0.0 to 600.0 s 0.0 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• Voltage fluctuation in the DC bus exceeded the level that trips KEB (set to S4-04). • Phase loss was detected as defined by the phase loss detection level (S4-08) and the detection time (S4-10). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 253
S4-11 is set below 1.35, the drive will reaccelerate without waiting for the time set in S4-12. The ramp time will not be S5-05 or the standard ramp, but will be calculated by the drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 254
KEB 2 begins when one of the conditions that triggers the KEB function becomes true. To have multiple drives remain in sync with one another while accelerating and decelerating during KEB 2, Yaskawa recommends setting a multi-function input to "KEB" (H1- = 65 or 66) to activate the synchronous accel/decel provided by KEB 2.
Page 255
Use KEB 2 (S4-01 = 2) to have all drive decelerate together. Name Setting Range Default S4-01 KEB Mode Selection 0 to 3 Setting 0: KEB Disabled Drive will not use KEB when power loss occurs. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 256
Note: 1. This parameter is disregarded by the drive is an input terminal is set for KEB (H1- = 65 or 66). 2. S4-06 must be set to higher value than S4-11. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 257
KEB may no longer be present, KEB will still continue until the time set to S4-13 has passed. Name Setting Range Default S4-13 KEB Minimum Operation Time 0 to 2000 ms 50 ms YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
2. S5-03 is set as a percentage of the output frequency just before the KEB function is triggered. It determines the point at which the drive switches between deceleration times while the KEB function is executed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 259
Sets the lower limit for the frequency reduction step at the start of KEB operation. The lower limit is calculated as Minimum Frequency Reduction = Motor rated slip (E2-02) × S5-11 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Enter the time required for the motor the drive is running to accelerate from zero up to the maximum frequency at the rated torque. If setting in parameter E2-11 is changed by the user or by performing Auto-Tuning, then S6-02 will automatically be set to the motor acceleration time of a standard Yaskawa 4-pole motor. Name...
Page 261
(S4-01 = 3). If oscillation occurs during Power KEB Ride-Thru, then gradually increase this setting in increments of 0.010 s. Name Setting Range Default S6-07 Torque Limit Delay Time 0.000 to 1.000 s Determined by A1-02 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
0.00 to 1.00 Hz 0.20 Hz u T: Motor Tuning Auto-Tuning automatically sets and tunes parameters required for optimal motor performance. Refer to Auto-Tuning on page 87 for details on Auto-Tuning parameters. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Refer to PID Block Diagram on page 129 for details on how these monitors display PID data. U5: PID Monitors on page 419 has a complete list of U5- monitors and descriptions. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
These parameters allow the user to monitor the voltage levels used for KEB function start and end. For more information on the U9 monitor parameter monitors, see U9: KEB Voltage Monitors on page 421. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 267
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. Check all the wiring after installing the drive and connecting other devices to ensure that all connections are correct.
Refer to the section below that corresponds to the motor control method used. Note: This section describes parameters that are commonly edited and may be set incorrectly. Consult Yaskawa for more information on detailed settings and fine-tuning the drive.
0.035 s <1> Motor stalling makes normal operation Motor parameters Check the motor parameter settings. impossible (E1- , E5- <1> Optimal settings will differ between no-load and loaded operation. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(ASR) cannot be increased. The inertia ratio between the load and motor and the acceleration time of the motor running alone must be set. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Check the digital operator for information about possible faults if the drive or motor fails to operate. Refer to Using the Digital Operator on page If problems occur that are not covered in this manual, contact the nearest Yaskawa representative with the following information: • Drive model •...
EF1 to EF8 External Fault (input terminal S1 to S8) Input Phase Loss EEPROM Write Error PG Disconnect (for Control Mode with PG) Internal Fan Fault PGoH PG Hardware Fault YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 274
Drive Disabled Run Command Input Error Option Card External Fault EF1 to EF8 External Fault (input terminal S1 to S8) Internal Fan Fault Excessive PID Feedback PID Feedback Loss YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 275
Control Method Selection Error oPE15 Torque Control Setting Error Multi-Function Analog Input Selection oPE07 oPE16 Energy Saving Constants Error Error oPE08 Parameter Selection Error oPE18 Online Tuning Parameter Setting Error YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 276
Voltage class and/or drive capacity does not match vFyE Parameter settings in the drive and those saved to the copy function are not the same vrFy Comparing parameter settings (flashing) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Control circuit is damaged. • If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 278
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up). Cause Possible Solution Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your Hardware is damaged. nearest sales representative.
Page 279
F6-03 = 3 “alarm only” (the drive continued to run • Remove the external fault input from the PLC. after external fault). Problem with the PLC program. Check the PLC program and correct problems. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 280
Refer to Diagnosing and Resetting Faults on page 303. • Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your Hardware problem.
Page 281
= 61 or 62) via one of the external terminals. Note: Speed Search 1 and 2 are the same when using PM OLV. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your Hardware problem.
Page 282
• Enter the correct motor code to E5-01. Loop Vector (Yaskawa motors only) or the motor data • If a non-Yaskawa PM motor is used, enter “FFFF” to E5-01. Set the correct motor data to the E5- parameters or perform are wrong.
Page 283
Possible Solution The option card installed into port CN5-B is Check if the drive supports the option card that you are attempting to install. Contact Yaskawa for assistance. incompatible with the drive. A communication option card has been installed in Communication option cards are supported by option port CN5-A only.
Page 284
The electrical thermal protection characteristics and • Correct the type of motor protection that has been selected (L1-01). motor overload characteristics do not match. • Install an external thermal relay. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 285
Fast acceleration time causes the motor to overshoot the • Use longer S-curve acceleration and deceleration times. speed reference. • Enable the Overvoltage Suppression function (L3-11 = 1). • Lengthen the S-curve at acceleration end. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 286
• Stabilize drive input power or disable phase loss detection. • Check the maintenance time for the capacitors (U4-05). • Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact Yaskawa or your nearest sales representative.
Page 287
• Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 303. • Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your The control circuit is damaged. nearest sales representative.
Page 288
Problem detected with the voltage on the output side of the drive. Cause Possible Solution Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your Hardware is damaged. nearest sales representative.
• Set a longer CE detection time (H5-09). Incompatible PLC software settings or there is a • Check the PLC. hardware problem. • Remove the cause of the error on the controller side. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 290
• Reconnect the signal line. • Check if the unused terminals have been set for H1- = 2C to 2F (External Fault). Multi-function contact inputs are set incorrectly. • Change the terminal settings. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 291
Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest Feedback input circuit is damaged. sales representative.
Page 292
Possible Solutions The main circuit and control circuit capacitors have Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest reached 90% of their expected performance life. sales representative.
Page 293
• Stabilize drive input power or disable phase loss detection. • Check the maintenance time for the capacitors (U4-05). • Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact Yaskawa or your nearest sales representative.
Page 294
Air inside the drive is too hot. Check the temperature inside the drive. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest The CHARGE light is broken or disconnected.
To load the parameter settings to the drive that are stored in the terminal board, set A1-03 to between the control board and the terminal board no longer match. 5550. Initialize parameters after drive replacement by setting A1-03 to 2220 or 3330. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 296
PID control is set to b5-01 = 3 or 4, but d2-02 (Frequency Reference Lower Limit) ≠ 0 or d2- Correct the parameter settings. 05 (Frequency Reference 2 Lower Limit) ≠ 5. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 297
• E2-02 has been set below 30% of the original default value Make sure E2-02, E2-03, and E2-06 are set the correct values. • E2-06 has been set below 50% of the original default value • E2-03 = 0 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(T1-02 and T1-04) do not match. • Correct the settings of parameters T1-02 and T1-04. The setting of parameter T1-04 is smaller than 0.3 A. Correct the settings of parameter T1-04. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 299
Error Name Er-11 Motor Speed Fault Cause Possible Solutions • Increase the acceleration time (C1-01). Torque reference is too high. • Disconnect the machine from the motor, if possible. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 300
• If a magnetic contactor is used between motors, make sure it is closed. • Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest The current is too low.
The device being used to write the parameters is blank and Making sure all connections are correct, and copy the parameter settings onto the USB Copy Unit or the operator. does not have any parameters saved on it. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 302
Comparing Parameter Settings (flashing) Cause Possible Solutions The Verify mode has confirmed that parameters settings on the drive and parameters read to the copy device are Not an error. identical. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Parameters U2-03 through U2-20 help determine the cause of a fault. Parameters to be monitored differ depending on the control mode. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. The Run command must first be removed before a fault situation can be cleared. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• Set a new password to parameter A1-05. • Check the drive input power voltage by looking at the DC bus voltage (U1-07). Undervoltage was detected. • Check all main circuit wiring. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Typically, forward is designated as being counterclockwise when looking from the motor shaft (see figure below). The forward direction for the motor is setup incorrectly. Forward Rotating Motor (looking down the motor shaft) Motor Shaft YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• Check if the mechanical brake is fully releasing as it should. Acceleration time has been set too long. Check if the acceleration time parameters have been set too long (C1-01, C1-03, C1-05, C1-07). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Switch to a larger capacity drive. rated current. u Load Falls When Brake is Applied Cause Possible Solutions Insufficient DC Injection Braking. Increase the amount of DC Injection Braking (b2-02). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Perform Auto-Tuning. Refer to Motor Performance Fine-Tuning on page 268. control modes). The control mode was changed after performing Auto-Tuning. Perform Auto-Tuning again. Only Stationary Auto-Tuning was performed. Perform Rotational Auto-Tuning. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• A relay should be set up to make sure the Run command remains enabled throughout any power loss. The relay that is supposed to maintain the Run command has been Check wiring and circuitry for the relay intended to keep the Run command enabled. switched off. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 313
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.
Page 314
Do not operate damaged equipment. Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Recommended Daily Inspection Table 7.1 outlines the recommended daily inspection for Yaskawa drives. Check the following items on a daily basis to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.
Recommended Periodic Inspection Table 7.2 outlines the recommended periodic inspections for Yaskawa drive installations. Although periodic inspections should generally be performed once a year; the drive may require more frequent inspection in harsh environments or with rigorous use. Operating and environmental conditions, along with experience in each application, will determine the actual inspection frequency for each installation.
When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. Yaskawa recommends checking the maintenance period regularly to ensure maximum performance life.
Page 318
If the Maintenance Monitor is not reset, the drive will not have the correct value of the performance life for the new component. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
NOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and could seriously damage the drive. To ensure maximum useful product life, replace all cooling fans when performing maintenance. Contact your Yaskawa representative or the nearest Yaskawa sales office to order replacement cooling fans or circulation fans as required.
2A0110 to 2A0415 4A0007 to 4A0044 4A0058 to 4A0362 A – Fan Cover B – Cooling Fan Figure 7.1 Cooling Fan Component Names: 2A0021 to 2A0415, 4A0007 to 4A0362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure 7.2 Removing the Fan Cover: 2A0021 to 2A0081, 4A0007 to 4A0044 Remove the cooling fan cartridge. Disconnect the pluggable connector and remove the fan. Figure 7.4 Figure 7.3 Removing the Cooling Fan: 2A0021 to 2A0081, 4A0007 to 4A0044 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 322
Figure 7.6 Reattach the Fan Cover: 2A0021 to 2A0081, 4A0007 to 4A0044 Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting o4-03 to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure 7.9 YEC_TMonly Lift the fan cover out of the drive leading with the back end. Figure 7.8 Removing the Cooling Fan: 2A0110 and 2A0138, 4A0058 and 4A0072 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 324
Front of drive Back of drive Cross-Section YEC_ Fan cover Back of drive TMonly Hook Hook Front of drive Figure 7.11 Reattach the Fan Cover: 2A0110 and 2A0138, 4A0058 and 4A0072 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Lift the cooling fan directly up on the fan as shown below. Unplug the relay connector and free the fan from the drive. Figure 7.15 YEC_ TMonly Figure 7.14 Removing the Cooling Fan: 4A0088 and 4A0103 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 326
Figure 7.18 Holes for connector tabs. Fan cover Four tabs Back or Drive YEC_ TMonly Hook Hook Front of Drive Figure 7.17 Reattach the Fan Cover: 4A0088 and 4A0103 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
D – Circulation Fan Relay Cable B – Fan Relay Cable E – Fan Connector (CN7) C – Fan Connector (CN6) Figure 7.19 Cooling Fan Replacement: Fan Unit and Connectors YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 328
4A0139, 4A0165, 4A0208 A – Fan Guard C – Cooling Fan B – Cable Cover D – Circulation Fan Figure 7.21 Fan Unit Disassembly: 2A0169 and 2A0211, 4A0139 and 4A0165 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 329
Connector for fan B2 Connector for fan B1 Figure 7.23 Cooling Fan Wiring: 2A0250, 2A0312 and 4A0208 Make sure that the protective tube does not stick out beyond the fan guard. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 330
Figure 7.25 Installing the Cooling Fan Unit: 2A0169 to 2A0415, 4A0139 to 4A0362 Reattach the covers and digital operator. Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting o4-03 to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Replace the entire drive if the main power circuitry is damaged. Contact your local Yaskawa representative for more information. Before replacing any individual parts of the drive, contact your local Yaskawa representative if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty policy.
Page 332
Slide the terminal board as illustrated by the arrows, and remove it from the drive along with the bottom cover. Figure 7.30 Figure 7.29 Drive Replacement: Remove the Terminal Board Figure 7.31 Figure 7.30 Drive Replacement: Removable Terminal Board Disconnected from the Drive YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 333
A1-03 to 5550. Reset timers used for the Maintenance Monitor function by setting parameters o4-01 through o4-12 back to 0, and parameter o4-13 to 1. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 334
7.5 Drive Replacement YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 337
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
8.2 Drive Options and Peripheral Devices Drive Options and Peripheral Devices The following table of peripheral devices lists the names of the various accessories and options available for Yaskawa drives. Contact Yaskawa or your Yaskawa agent to order these peripheral devices.
<3> When using an external braking chopper in drives from CIMR-T 2A0004 to 0138 and CIMR-T 4A0002 to 0072 connect the chopper to drive terminals B1 and -. When using larger drives connect the chopper to terminals +3 and -. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
D – Drive grounding terminal (FE) J – Front cover E – Insert connector CN5 here K – Digital operator F – Option card L – Terminal cover Figure 8.2 Installing an Option Card YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 341
Place the front cover and digital operator back onto the drive. Note: Leave enough space when wiring so that the front cover can be easily reattached. Make sure no wires get caught between the front cover and the drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Enable the drive’s braking resistor overload protection by setting L8-01 = 1 when using ERF type resistors. Figure 8.5 Drive Braking Resistor Figure 8.5 Connecting a Braking Resistor: ERF Type YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 343
Use this input to trigger a fault in the drive in case a CDBR or braking resistor overload occurs. Disable dynamic braking transistor protection by setting L8-55 = 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• If several drives are connected to one MCCB, use a sequence that shuts the power OFF when an error occurs in one drive by using magnetic contactor (MC) as shown in the following figure. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
• Install noise filters on the input and output side of the drive, install the drive in a metal enclosure panel and use a shielded motor cable to reduce radiated noise. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 347
This drive is tested according to European standards IEC61800-5-1 and complies with the EMC guidelines. Refer to EMC Filter Installation on page 477 for details about EMC filter selection and installation. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 348
Figure 8.15 MCCB R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 A – Power supply C – Output-side noise filter B – Drive D – Motor Figure 8.15 Output-Side Noise Filter YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified. Yaskawa recommends installing a fuse to the input side of the drive to prevent damage to the drive if a short circuit occurs.
WARNING! Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting. Check local electrical codes before making adjustments to motor thermal overload settings. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier frequency, and current limit. The default setting is for HD (C6-01 = 0). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
400 Hz <8> <1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
Maximum Output Frequency (Hz) <7> <1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
Two Safe Disable inputs and 1 EDM output according to ISO13849-1 Cat.3 PLd, IEC61508 SIL2, Insulation coordination: class Safety Standard Note: Time from input open to drive output stop is less than 1 ms Protection Design IP20 enclosure YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 356
<9> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground fault is present at the output. <10> Up to 3000 m with output current and voltage derating. Refer to Altitude Derating on page 361 for details. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<1> These values assume the carrier frequency is set to 8 kHz or less. <2> These values assume the carrier frequency is set to 5 kHz or less. <3> These values assume the carrier frequency is set to 2 kHz. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Figure A.3 Carrier Frequency Derating (CIMR-T 4A0002 to 4A0103) Figure A.4 Normal Duty 4A0139 to 4A0362 Heavy Duty 70% of HD 2 kHz 5 kHz 10 kHz Figure A.4 Carrier Frequency Derating (CIMR-T 4A0139 to 4A0362) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Drive operation between -10°C and 30°C allows 100% continuous current without derating. Operation between 30°C and 50°C requires output current derating. Figure A.6 Drive Rating L8-35=1: Side-by-Side Mounting L8-12 (Ambient temp: °C) Figure A.6 Ambient Temperature and Installation Method Derating (L8-35 = 1) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m both the drive rated voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 362
A.6 Drive Derating Data YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Refers to a second motor when the drive is operating two motors. Switch between these motors using the multi-function input terminals. Note: If a parameter is not available in a certain control mode, the symbol for that control mode is grayed out. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Digital Input Card (DI-A3) Analog Monitor Card (AO-A3) Digital Output Card (DO-A3) Communication Option Card Multi-Function Digital Inputs Multi-Function Digital Outputs Multi-Function Analog Inputs Multi-Function Analog Outputs MEMOBUS/Modbus Serial Communication YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 366
Synchronous Operation Induction Motor Auto-Tuning PM Motor Auto-Tuning ASR and Inertia Tuning Operation Status Monitors Fault Trace Fault History Maintenance Monitors PID Monitors Operation Status Monitors KEB Voltage Monitors YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. Min: 0 (126H) Selection 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2- Max: 1 17 through A2-32 for quick access. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
0: Disregarded. A new Run command needs to be issued after power up. Max: 1 1: Allowed. Motor will start immediately after power up if a Run command is already enabled. <39> The setting range is 0 to 1 in CLV. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 369
Min: 0.0 Search Max: 2.0 Sets the current injected to the motor at the beginning of Speed Estimation Speed Search. Set as a coefficient for the motor rated current. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 370
Sets the proportional gain of the PID controller. Max: 25.00 b5-03 Default: 1.0 s (1A7H) All Modes Integral Time Setting (I) Min: 0.0 s Sets the integral time for the PID controller. Max: 360.0 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 371
All Modes Default: 0.00% (19FH) PID Output Lower Limit Min: -100.0% Sets the minimum output possible from the PID controller as a percentage of the maximum Max: 100.0% output frequency. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 372
V/f w/PG Default: 20 ms b8-05 Power Detection Filter Time Min: 0 ms OLV/PM AOLV/PM CLV/PM (1D0H) Max: 2000 ms Sets a time constant filter for output power detection. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Sets the time to accelerate from 0 to maximum frequency. C1-08 (207H) Deceleration Time 4 (Motor 2 All Modes Decel Time 2) Sets the time to decelerate from maximum frequency to 0. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 374
Motor 2 Slip Compensation Limit Min: 0% (242H) Max: 250% Sets the upper limit for the slip compensation function for motor 2. Set as a percentage of the motor rated slip (E4-02). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 375
ASR Primary Delay Time Constant Min: 0.000 s OLV/PM AOLV/PM CLV/PM (220H) Max: 0.500 s Sets the filter time constant for the time from the speed loop to the torque command output. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 376
Motor 2 Inertia Min: 0.0001 kgm (278H) Max: 600.00 kgm Sets the inertia of motor 2 alone without the load. This value is automatically set during ASR or Inertia Auto-Tuning. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 377
<1> Default setting value is dependent on the drive model (o2-04), the control mode (A1-02), and the Drive Duty (C6-01). <5> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Min: 0 (29AH) 0: Speed Control Max: 1 1: Torque Control Set to 0 when using a digital input to switch between Speed and Torque Control (H1- = 71). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 379
Added to the frequency reference when the digital input “Frequency offset 3” (H1- = 46) is Max: 100.0% switched on. Set as a percentage of the maximum output frequency. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Sets the no-load current for the motor. Automatically set during Auto-Tuning. V/f w/PG Default: 4 E2-04 Number of Motor Poles Min: 2 OLV/PM AOLV/PM CLV/PM (311H) Max: 48 Sets the number of motor poles. Automatically set during Auto-Tuning. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 381
E3-01 Motor 2 Control Mode Selection Min: 0 0: V/f Control (319H) Max: 3 1: V/f Control with PG 2: Open Loop Vector Control 3: Closed Loop Vector Control YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 382
V/f w/PG Default: <24> E4-11 Motor 2 Rated Power Min: 0.00 kW OLV/PM AOLV/PM CLV/PM (327H) Max: 650.00 kW Sets the motor rated capacity in kW. Automatically set during Auto-Tuning. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<19> <24> <34> (329H) Motor Code Selection Enter the Yaskawa motor code for the PM motor being used. Various motor parameters are Min: 0000 <16> automatically set based on the value of this parameter. Setting that were changed manually will Max: FFFF <37>...
Page 384
Sets the time required to trigger a PG Open fault (PGo). V/f w/PG Default: 10 F1-18 OLV/PM AOLV/PM CLV/PM dv3 Detection Selection Min: 0 (3ADH) Max: 10 0: Disabled 1: Enabled YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 385
Sets the gain for the input signal to the analog card. Max: 999.9% F2-03 Default: 0.0% (369H) All Modes Analog Input Option Card Bias Min: -999.9% Sets the bias for the input signal to the analog card. Max: 999.9% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 386
Min: 0 (397H) All Modes Max: 1 0: 0 to 10 V Default: 0 F4-08 1: -10 to 10 V Terminal V2 Signal Level Min: 0 (398H) Max: 1 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 387
Sets the station address when the MECHATROLINK-II option has been installed. Max: 3FH common_ All Modes Default: 0 TMonly F6-21 MECHATROLINK Frame Size Min: 0 – (36CH) 0: 32 byte Max: 1 1: 17 byte YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those terminals will create a multi-step speed sequence using the frequency references set in d1-01 through d1-08. Multi-Step Speed Reference 3 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 389
Accel/decel time selection 2 Used in conjunction with an input terminal set for “Accel/decel time selection 1” (H1- = 7), and allows the drive to switch between accel/decel times 3 and 4. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 390
Closed: Assigns the same accel/decel times to all motors in the line so that they reach the desired frequency at the same time. V/f w/PG Energy Saving On/Off OLV/PM AOLV/PM CLV/PM Closed: Enables the Energy Saving function. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 391
CLV/PM Open: Short Circuit Braking enabled V/f w/PG Forward/reverse detection (V/f Control OLV/PM AOLV/PM CLV/PM with Simple PG feedback) Direction of rotation detection (for V/f with Simple PG Feedback) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 392
Set this value when using the terminal in the pass-through mode. All Modes Minor fault Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 393
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being performed). All Modes Drive enabled Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 394
(412H) All Modes Terminal A1 Bias Setting Min: -999.9% Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1. Max: 999.9% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 395
10 V = E1-04 (maximum output frequency) V/f w/PG Output voltage bias OLV/PM AOLV/PM CLV/PM 10 V = E1-05 (motor rated voltage) All Modes Accel/decel time gain 10 V = 100% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 396
Selects the data to be output through multi-function analog output terminal FM. Min: 000 (41DH) Terminal FM Monitor Selection Set the desired monitor parameter to the digits available in U - . For example, enter “103” Max: 999 for U1-03. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 397
Max: 10.0 s networking several drives. All Modes Default: 0 H5-10 Unit Selection for MEMOBUS/ Min: 0 (436H) Modbus Register 0025H 0: 0.1 V units Max: 1 1: 1 V units YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Selection (PTC input) 0: Ramp to stop Max: 3 1: Coast to stop 2: Fast Stop (decelerate to stop using the deceleration time in C1-09) 3: Alarm only (“oH3” will flash) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 399
3: Stall Prevention with braking resistor. Stall Prevention during deceleration is enabled in coordination with dynamic braking. 4: Overexcitation Deceleration 1. Decelerates while increasing the motor flux. 5: Overexcitation Deceleration 2. Adjust the deceleration rate according to the DC bus voltage. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 400
All Modes Default: 0 L4-07 Speed Agreement Detection Min: 0 0: During run only (no detection while drive output is shut off) (470H) Selection Max: 1 1: Detection always enabled. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 401
Default: 0.1 s (4A6H) All Modes Torque Detection Time 2 Min: 0.0 s Sets the time an overtorque or undertorque condition must exist to trigger torque detection 2. Max: 10.0 s YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 402
Sets a delay time to shut off the cooling fan after the Run command is removed when L8-10 = 0. Default: 40°C L8-12 All Modes Ambient Temperature Setting Min: -10°C (4B8H) Enter the ambient temperature. This value adjusts the oL2 detection level. Max: 50°C YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 403
<24> Default setting is determined by the drive model (o2-04) and duty selection (C6-01). <27> Default setting is determined by the control mode (A1-02) and the drive model (o2-04). <34> Default setting is determined by the control mode (A1-02). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
OLV/PM AOLV/PM CLV/PM n3-23 Overexcitation Operation Min: 0 (57BH) Selection 0: Enabled in both directions Max: 2 1: Enabled only when rotating forward 2: Enabled only when in reverse YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 405
Current Max: 200% Sets the d-axis current reference during acceleration/deceleration as a percentage of the motor rated current. Set to a high value when more starting torque is needed. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 406
Sets the frequency at which the drive stops compensating the output voltage for the IGBT On- (650H) Frequency Max: E1-04 Delay. <9> Default setting value varies by the drive model (o2-04). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
0: Forward Min: 0 (527H) Using Operator 1: Reverse Max: 1 This parameter requires that drive operation be assigned to the digital operator. o2-09 Reserved – – – (50DH) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
AOLV/PM CLV/PM Disturb Step Min: 0.0% Max: 50.0% Sets the step applied at the end of disturb acceleration or deceleration as a percentage of the Disturb amplitude in S1-02. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 409
Sets the DC bus voltage level at that the drive assumes the power supply has returned. If this level is exceeded for longer than S4-07 the drive starts reaccelerating to the set frequency Max: 200.0% reference. The setting value depends on the selection in parameter S4-02. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 410
Sets the output frequency reduction step applied when power loss is detected during Max: 300% acceleration. Percent of frequency reduction = (slip frequency just before KEB) × S5-08 × 2 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 411
Max: 1.00 Hz Once the motor is done coasting, the drive will apply the motor speed detection value if the value detected is less than S9-06 plus the previous value. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
(Stationary Auto-Tuning) Max: 20.00 Hz After setting the motor capacity to T1-02, this parameter will automatically display the motor slip for a standard 4 pole Yaskawa motor. Enter the motor slip as indicated on the motor test report. V/f w/PG Default: 14 W <31>...
Page 413
T2-02 PM Motor Code Selection Min: 0000 Enter the motor code when using a Yaskawa PM motor. Once the motor code is entered, the (751H) Max: FFFF drive automatically sets parameters T2-03 through T2-14. When using a motor that is not supported motor code or a non-Yaskawa motor, set FFFF here and then adjust the other T2 parameters according the motor nameplate or the motor test report.
<7> <24> (762H) Motor Inertia Min: 0.0001 kgm OLV/PM AOLV/PM CLV/PM <33> Max: 600.00 kgm Sets the motor inertia. Default setting is the inertia of a Yaskawa motor. V/f w/PG T3-04 Default: 10.0 Hz OLV/PM AOLV/PM CLV/PM (763H) System Response Frequency Min: 0.1 Hz...
Page 415
No signal output Multi-Function Output Terminal Status – – (4AH) available Digital Output (terminal M3-M4) Multi-Function Digital Output (terminal M5-M6) Not Used Fault Relay (terminal MA-MC closed MA-MC open) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 416
A.3) and one decimal place (0.1 kW) if the set Maximum Applicable Motor Capacity is higher than 11 kW. <41> When using V/f Control, 10 V is the drive capacity in kW. When using one of the vector control modes, 10 V is the motor capacity (E2-11). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 417
<49> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current. Note: Fault trace (i.e., the fault history) is not kept when CPF00, CPF01, CPF06, CPF24, Uv1, Uv2, Uv3, oFA00, oFB00, oFC00 occur. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 418
(5DH) available U4-11: 12345 MWh All Modes U4-13 No signal output 0.01 A Peak Hold Current – (7CFH) available <49> Displays the highest current value that occurred during run. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 419
Displays the difference of both feedback values if differential feedback is used (U5-01 - U5-05). If differential feedback is not used, then U5-01 and U5-06 will be the same. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 420
10 V: No. of pulses Zero Servo Pulse Movement – OLV/PM AOLV/PM CLV/PM (62H) per revolution Displays how far the rotor has moved from its last position in PG pulses (multiplied by 4). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 421
Displays the residual voltage detected by the Synchronous Operation Function (b3-24 = 3). <15> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<3> This setting value depends on a Maximum Applicable Motor Capacity. <4> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 423
<4> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (-100.0 to 100.0%) instead of in Hz. <5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <2> Default setting is determined by the drive model (o2-04) and duty selection (C6-01). YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Motor Acceleration Time 0.178 0.142 0.142 0.142 0.166 0.145 μs n9-12 On-Delay Compensation Time μF S6-01 DC Bus Capacity 1000 1000 S6-02 Motor Acceleration Time 0.178 0.142 0.142 0.142 0.166 0.145 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 426
On-Delay Compensation Time μF S6-01 DC Bus Capacity 2670 2670 3600 3600 4980 4980 6000 6000 S6-02 Motor Acceleration Time 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 427
On-Delay Compensation Time μF S6-01 DC Bus Capacity 17400 17400 24600 24600 21600 21600 33000 33000 S6-02 Motor Acceleration Time 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 428
0.154 0.154 0.168 0.168 0.175 0.175 0.265 μs n9-12 On-Delay Compensation Time μF S6-01 DC Bus Capacity S6-02 Motor Acceleration Time 0.145 0.154 0.154 0.168 0.168 0.175 0.175 0.265 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 429
μF S6-01 DC Bus Capacity 2500 2500 2900 2900 3300 3300 4000 4000 4000 4000 S6-02 Motor Acceleration Time 0.323 0.32 0.32 0.387 0.387 0.317 0.317 0.533 0.533 0.592 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 430
On-Delay Compensation Time μF S6-01 DC Bus Capacity 7400 7400 6400 6400 7750 7750 11000 11000 S6-02 Motor Acceleration Time 0.592 0.646 0.646 0.673 0.673 0.777 0.777 0.864 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Motor Inertia 0.0007 0.0014 0.0021 0.0032 n5-02 Motor Acceleration Time 0.137 0.132 0.132 0.122 n8-49 d-Axis Current for High Efficiency Control S6-02 Motor Acceleration Time 0.137 0.132 0.132 0.122 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Data length 8 bit (fixed) Communication Parameters Parity Select even, odd, or none Stop bit 1 bit (fixed) Protocol MEMOBUS/Modbus (using RTU mode only) Max Number of Slaves 255 drives YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Note: 1. Turn on the DIP switch on the drive that is located at the end of the network. All other slave devices must have this DIP switch set to the OFF position. 2. Set H5-07 to “1” when using the RS-485 interface. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not located at the network line end. Refer to MEMOBUS/Modbus Termination on page 67 for details on setting S2. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Setting 0: Ramp to stop (uses the deceleration time currently enabled) Setting 1: Coast to stop Setting 2: Fast Stop (uses the deceleration time in C1-09) Setting 3: Alarm only (continue operation) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 451
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H. Name Setting Range Default H5-10 Unit Selection for MEMOBUS/Modbus Register 0025H 0 or 1 Setting 0: 0.1 V units Setting 1: 1 V units YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 452
Setting 1: Run/Stop, FWD/REV Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Refer to Setting 2: External reference 1/2 selection on page 183 for instructions on how to select external reference 1 and 2. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Increase H5-06 if the drive response causes overrun in the master. Figure C.7 PLC→Drive Drive→PLC PLC→Drive Command message Response message Command message Time H5-06 24 bit length setting Figure C.7 Minimum Response Wait Time YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Continue with steps 3 to 5 until the last data has been processed. The result of the last shift or XOR operation is the checksum. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 456
To be sure that the data is valid, perform a CRC-16 calculation on the response message data as described above. Compare the result to the CRC-16 checksum that was received within the response message. Both should match. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Function Code Function Code Upper Upper Error Code Test Code Test Code Lower Lower Upper CRC-16 Upper Upper Lower Data Data Lower Lower Upper Upper CRC-16 CRC-16 Lower Lower YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Lower Starting Data Lower Upper Next Data Lower Upper CRC-16 Lower Note: For the number of bytes in the command message, take double the number of the data quantity. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
3 Output Phase Loss (LF) bit 4 Braking Resistor Overheat (rH) bit 5 Reserved bit 6 Motor Overheat 2 (PTC input) (oH4) bit 7 to bit F Reserved YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 461
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency 0039H PID Input, 0.1% units, signed, 100% / max. output frequency 003AH PID Output, 0.1% units, signed, 100% / max. output frequency 003BH, 003CH Reserved YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 462
Frequency Reference After Soft- starter (U1-16) 00B6H 0.01% units 00B7H r/min <4> Frequency Reference 00B8H 0.01% units 00B9H to 00BEH Reserved 00BFH Lists the last to digits of operation error code oPE YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 463
6 to B Reserved bit C Output Voltage Detection Fault (voF) bit D Braking Resistor Fault (rF) bit E Braking Transistor Overload Fault (boL) bit F Motor Overheat (NTC Input) (oH5) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 464
External Fault 1 (input terminal S1) (EF1) bit 9 External Fault 2 (input terminal S2) (EF2) bit A Safe Disable Input (HbbF) bit B Safe Disable Input (Hbb) bit C to F Reserved YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 465
Same type of option card already connected (oFA02) 00D8H bit 3, 4 Reserved bit 5 A/D Conversion Error (oFA05) bit 6 Option Response Error (oFA06) bit 7 to F Reserved YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 466
Control Response Selection 1 Error (oFb40) bit B Drive timeout waiting for response (oFb41) bit C Control Response Selection 2 Error (oFb42) bit D Control Response Selection Error (oFb43) bit E, F Reserved YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 467
Reserved bit C Multi-Function Digital Input S5 bit D Multi-Function Digital Input S6 bit E Multi-Function Digital Input S7 bit F Multi-Function Digital Input S8 0002H Frequency Reference 30000/100% YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
11 determines if an Enter command is needed or not in order to activate parameter changes in the drive. • If upgrading from a G7 or F7 series drive to an T1000A, set parameter H5-11 to 0. • If upgrading from a V7 series drive to an T1000A, set parameter H5-11 to 1.
• When the command message data length is invalid. Note: If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages to the master. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Set back jumper S3 to its original position. Set terminal S6 to its original function. Return to normal operation. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 475
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices.
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded systems, contact your Yaskawa representative for instructions. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive also comply with EMC guidelines. Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards. Place the drive and EMC noise filter in the same enclosure.
Page 478
K – Make sure the ground wire is grounded F – Motor cable (braided shield cable, max. 10 m) Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 480
400 V Three-Phase Units 4A0002 3.2 A UZDA-B 28 mH 4A0004 Note: Drive models not listed in the table above do not require a DC reactor for EMC compliance. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Do not install the drive to an area greater than pollution degree 2 (UL standard). Main Circuit Terminal Wiring Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-T 2A0110 to 2A0415 and 4A0058 to 4A0362.
Page 482
(283 to 354) –, +1 – 70 to 150 2A0312 18 to 23 <1> – 70 to 150 (159 to 204) 32 to 40 95 to 150 (283 to 354) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 483
–, +1, +2 – 6 to 16 4A0038 2 to 2.5 B1, B2 – 6 to 10 (17.7 to 22.1) 4 to 6 6 to 16 (35.4 to 53.1) YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 484
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 485
D.3 UL Standards Closed-Loop Crimp Terminal Recommendations Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of crimp terminals when wiring the drive main circuit terminals on models CIMR-T 2A0110 to 2A0415 and 4A0058 to 4A0362.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection (L1-01 = 0) and wire each motor with its own motor thermal overload relay. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 488
Figure D.7 Time (min) Cold Start Hot Start Motor Current (%) (E2-01=100 %) Figure D.7 Motor Overload Protection Time YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Use the table below to match drive models and capacitor cover. Capacitor covers can be ordered from a Yaskawa representative or directly from the Yaskawa sales department. The table below lists available capacitor covers.
Sinking/Sourcing Mode Selection for Safe Disable Inputs on page The Safe Disable Monitor uses a single channel photocoupler output. Refer to Output Terminals on page 61 for signal specifications when using this output. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 491
When Safe Disable was activated during run, first the Run command has to be removed and then the Safe Disable inputs have to be turned on before the drive can be restarted. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 492
This display should not appear under normal conditions if the Safe Disable circuit is utilized properly. Refer to Alarm Codes, Causes, and Possible Solutions on page 289 to resolve possible errors. YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
PM Motor Base Frequency d-Axis Inductance Number of PM Motor Poles q-Axis Inductance PM Motor Base Speed r/min Motor Speed Encoder (if used) Items Value Items Value Manufacturer Resolution Interface YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Setting Value and Function Name Memo M1-M2 H2-01 = M3-M4 H2-02 = M5-M6 H2-03 = u Monitor Outputs Terminal Output Used Setting Value and Function Name Memo H4-01 = H4-04 = H6-06 = YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Search Operation Voltage Limit b3-27 Start Speed Search Select b8-16 Energy Saving Parameter (Ki) for PM Motors b4-01 Timer Function On-Delay Time b8-17 Energy Saving Parameter (Kt) for PM Motors YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 497
V/f Pattern Selection C5-17 Motor Inertia E1-04 Maximum Output Frequency C5-18 Load Inertia Ratio E1-05 Maximum Voltage C5-21 Motor 2 ASR Proportional Gain 1 E1-06 Base Frequency E1-07 Middle Output Frequency YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 498
PG 1 Signal Selection H2-03 Terminal M5-M6 Function Selection F1-30 PG Option Card Port for Motor 2 Selection H2-06 Watt Hour Output Unit Selection F1-31 PG 2 Pulses Per Revolution YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 499
Output Ground Fault Detection Selection L1-05 Motor Temperature Input Filter Time (PTC input) L8-10 Heatsink Cooling Fan Operation Selection L1-13 Continuous Electrothermal Operation Selection L8-11 Heatsink Cooling Fan Off Delay Time YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 500
User Monitor Selection After Power Up S5-01 KEB Decel Time 1 o1-03 Digital Operator Display Selection S5-02 o1-04 V/f Pattern Display Unit KEB Decel Time 2 o1-10 User-Set Display Units Maximum Value YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 501
PG Number of Pulses Per Revolution for PM Motor T2-16 Tuning T2-17 Encoder Z-Pulse Offset T3-01 Inertia Tuning Frequency Reference T3-02 Inertia Tuning Reference Amplitude T3-03 Motor Inertia T3-04 ASR Response Frequency YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Ambient Temperature and Installation Method Derating. 360, 361 200 V, 1150 r/min Type Yaskawa SST4 Series Motor ..441 Ambient Temperature Setting....231, 360, 401 200 V, 1450 r/min Type Yaskawa SSR1 Series Motor.
Page 503
Control Method Selection Error ......296 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 504
Drive Capacity Setting Fault ......295 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 505
European Standards ....... . . 474 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 506
H4-07 ..........67 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 507
Installation Method Selection......232 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 508
Motor 2 ASR Limit ....... . . 151 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 509
Motor Poles ........91 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 510
Output Current Imbalance ......281 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 511
PID Setpoint ........418 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 512
Pulse Train Monitor Selection ......210 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 513
Stationary Auto-Tuning 2 ......87 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Three-phase 400 V: CIMR-T 4A0139 to 4A0362 Revision: Reviewed and corrected entire documentation. Upgraded the software version to S6002. Revision: Address, format Back cover − − February 2009 First Edition YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Page 517
Phone: +44 (0)12 36 735 000 Fax: +44 (0)12 36 458 182 U.S.A. YASKAWA AMERICA, INC. 2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (927-5292) or +1 847 887 7000 Fax: +1 847 887 7310 Internet: http://www.yaskawa.com JAPAN YASKAWA ELECTRIC CORPORATION...