YASKAWA T1000V Technical Manual page 327

Ac drive for textile applications
Table of Contents

Advertisement

No.
Name
C3-01
Slip Compensation Gain
<15>
C3-02
Slip Compensation Primary
Delay Time
<15>
C3-03
Slip Compensation Limit
Slip Compensation
C3-04
Selection during
Regeneration
Output Voltage Limit
C3-05
Operation Selection
C4-01
Torque Compensation Gain
<16>
Torque Compensation
C4-02
Primary Delay Time
Torque Compensation at
C4-03
Forward Start
Torque Compensation at
C4-04
Reverse Start
Torque Compensation Time
C4-05
Constant
Torque Compensation
C4-06
Primary Delay Time 2
C5 parameters are available only when using V/f Control with Simple PG Feedback (H6-01 = 3).
C5-01
ASR Proportional Gain 1
<15>
C5-02
ASR Integral Time 1
<15>
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Description
C3: Slip Compensation
Use C3 parameters to configure the slip compensation function.
Sets the slip compensation gain. Decides for what
amount the output frequency is boosted in order to
compensate the slip.
Note: Adjustment is not normally required.
Adjusts the slip compensation function delay time.
Decrease the setting when the slip compensation
response is too slow, increase it when the speed is not
stable.
Disabled when Simple V/f Control with PG (H6-01 = 3)
is used.
Sets the slip compensation upper limit. Set as a
percentage of motor rated slip (E2-02). Disabled when
Simple V/f Control with PG (H6-01 = 3) is used.
Selects slip compensation during regenerative operation.
0: Disabled
1: Enabled
Using the Slip Compensation function during
regeneration may require a braking option to handle
momentary increasing regenerative energy.
Selects if the motor magnetic flux is reduced during
output voltage saturation.
0: Disabled
1: Enabled
C4: Torque Compensation
Use C4 parameters to configure Torque Compensation function.
V/f Control: Sets the gain for the automatic torque
(voltage) boost function and helps to produce better
starting torque.
Increase this setting when using a long motor cable or
when the motor is significantly smaller than the drive
capacity.
Decrease this setting when motor oscillation occurs. Set
the value so that the current at low speed does not
exceeds the drives rated current.
Open Loop Vector: Sets the torque compensation
function gain. Normally no change is required.
Sets the torque compensation filter time.
Increase this setting when motor oscillation occurs.
Reduce the setting if there is not enough response from
the motor.
Sets torque compensation at forward start as a
percentage of motor torque.
Sets torque compensation at reverse start as a percentage
of motor torque.
Sets the time constant for torque compensation at
forward start and reverse start (C4-03 and C4-04). The
filter is disabled if the time is set to 4 ms or less.
Sets the torque compensation time 2. When an ov fault
occurs with sudden load changes or at the and of an
acceleration, increase the setting.
Note: Adjustment is not normally required. If adjusted
then AFR time 2 (n2-03) should be adjusted too.
C5: Automatic Speed Regulator
Use C5 parameters to configure the Automatic Speed Regulator (ASR).
Sets the proportional gain of the speed control loop
(ASR).
Sets the integral time of the speed control loop (ASR).
B.3 Parameter Table
Control
Mode
Range
Def.
V/f OL
P
V
M
0.0
0.0 to 2.5
A A −
<2>
2000
A A −
0 to 10000
ms
<2>
200% A A −
0 to 250
A A −
0,1
0
− A −
0,1
0
1.00
0.00 to 2.50
A A A
<2>
200 ms
0 to 60000
A A A
<2>
− A −
0.0 to 200.0 0.0%
-200.0 to
− A −
0.0%
0.0
0 to 200
10 ms – A
0 to 10000 150 ms – A
0.00 to
0.20
A
300.00
0.000 to
0.200 s A
10.000
Addr.
Pg.
Hex
20F
136
210
136
211
136
212
136
213
137
215
137
216
137
217
138
218
138
219
138
21A
138
B
21B
139
21C
139
327