C.5 MEMOBUS/Modbus Setup Parameters
H5-11: Communications Enter Function Selection
Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus communications.
Enter Command on page
No.
H5-11
Setting 0: Enter Command Necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last
parameter change, not for each single parameter (such as in Varispeed F7).
Setting 1: Enter Command not Necessary
Parameter value changes become effective immediately without the need to send an Enter command (such as in
Varispeed VS606-V7)
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications (b1-02
or b1-16 = 2).
No.
H5-12
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start
and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.
388
404.
Name
Communications Enter Function Selection
Name
Run Command Method Selection
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting Range
Determined by
0 or 1
Setting Range
0 or 1
Refer to
Default
o2-09
Default
0